Owner's manual

Electrical installation
Important notes
6
47
EDK84AZESxx DE/EN/FR/ES/IT 4.0
6 Electrical installation
6.1 Important notes
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Switch off the power supply and wait for at least three minutes
before working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
Danger!
Hazardous electrical voltage
For the variants E84AZESxxxxxSDand E84AZESxxxxxLD the
discharge current to PE is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when touching the device in case of a
fault.
Protective measures:
ƒ Implement the measures required in EN 61800−5−1, especially:
Fixed installation
The PE connection must comply with the standards (PE
conductor diameter ³ 10 mm
2
or use a double PE conductor)