User guide
5 Commissioning
Initial switch−on
EDK82ZAFLC−010 DE/EN/FR 4.0
44
H1inbet−statusanzeige
Initial switch−on
Note!
ƒ The standard device is only ready for operation if a HIGH level is applied to
terminal 28 (controller enable via terminal).
– Please note that the controller can be inhibited by various sources. The
sources act like a series connection of switches.
– If the drive does not start even though the controller has been enabled
via terminal 28, check whether the controller has been inhibited by
another source. Another source could be the key on the keypad.
ƒ Please note the different status information for code C0068 compared to
software version "0.1" (see the following table).
Bit Function Description
8 RFR (controller enable) 0: no controller enable
1: controller enable
11 IMP (pulse inhibit) 0: pulses for power sections inhibited
1: pulses for power sections enabled
15 TRIP (fault) 0: no fault
1: fault exists