12 Visualisation with »VisiWinNET®«
12.4 Use the Direct driver "LogicAndMotionV3" (local visualisation)
103
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4. Configure the added communication channel:
•A Line must be activated and the PLC address (node address) of the Controller must be
specified.
The PLC address and the IP address of the target device (Controller) must be specified.
(Preset IP address of the Controller: 192.168.5.99)
Note: The PLC address can be found in the »PLC Designer« in the context menu of the
device: DeviceCommunication SettingsIPC:Node Address
Further information on the configuration of the communication channel can be found in
the »VisiWinNET®« online help. Click the Help button to call the online help.
5. In a next step, you can browse variable definitions:
Using the variables browser to access variables (browse variables)
( 105)
6. After completion of the project configuration, the Project Explorer is provided with a new
channel: "LogicAndMotionV3".