Manual

ASPL 13.1001 DE/EN/FR/IT/ES 1.0
13
KFZ_Zeichen_EN-verdrahtung-bremse-AC-Mot-LKA
Operation on the frequency inverter
Note!
A label in the terminal box shows the limit values of the
voltages for your motor.
ƒ During operation of the motors on the frequency inverter or during switching
operationonthemains
voltage peaks can occur, which can damage the motor insulation.
ƒ In order to avoid malfunctions, the limit values specified
in the table must not be exceeded:
Application of the motor on the
Limit values for voltage peaks
Max. amplitude
û[kV]
Max. rate of rise
du/dt [kV/μs]
Frequency inverter,
single-phase
0.75
5
Frequency inverter, three-phase 1.5
Mains (switching operation) 0.75
Tip!
ƒ For switching operation on the mains you can limit the voltage peaks by
means of a suppressor circuit with RC elements or varistors (not included
in the scope of supply).
ƒ Dimension the suppressor circuit for the respective application case!