User Guide

21
Table 5. Lennox Smart Air Quality Monitor Alert Codes
Alert
ID
Source
device
Causing
Alert
Alert Code
Message
Priority
Condition
Troubleshooting Clear Condition
80001 Thermostat
IAQ: Persistent
Poor Air Quality
Information
only Dealer
Cycle power to device. To cycle
power, remove device from the wall
and disconnect the R terminal and
then reconnect.
If cycling power does not resolve
the issue, check all installed
Indoor Air Quality (IAQ) equipment
installed in the HVAC system. For
example check:
» All installed IAQ equipment are
power on, connected and working
properly.
» HC air lters and replace if dirty.
» PureAir or PureAir S UV lamp and
if not working replace. Check lter
and replace if dirty.
» ERV/HRV lter and replace if dirty.
» UV Germicidal lamp is working
and replace if necessary.
If cycling power and checking
all installed IAQ equipment
does not resolve the issue,
then replace the SAQM.
Automatically clears when
the system detects that the
issue no longer exists.