User Guide
Table Of Contents
- Shipping and Packing List
- Optional Accessories
- Introduction
- Terminology
- Installation Considerations
- Overview
- Downloading Lennox Smart Technician App
- Installation
- Adding SAQM
- Management - Replace, Remove and Factory Reset
- Dimensions, Operating and Storage Specifications
- Thermostat Alert Codes for the Smart Air Quality Monitor
- Lennox Smart Air Quality Monitor Troubleshooting
- FCC Compliance Statement
19
Table 5. Lennox Smart Air Quality Monitor Alert Codes
Alert
ID
Source
device
Causing
Alert
Alert Code
Message
Priority
Condition
Troubleshooting Clear Condition
70001 SAQM
IAQ: Internal
Sensor Fault
Service Soon
This issue will occur when:
• Any of the carbon dioxide,
volatile organic compounds and
Particulate Matter 2.5 sensors
output experiences an internal
communication outage.
• Collected data values are out of
range.
Cycle device power may clear
condition.
To cycle power, remove device
from the wall and disconnect the R
terminal and then reconnect.
If cycling power does not resolve
issue then:
• Remove device from the smart
devices network.
• Perform a factory reset of the
device. See "Factory Reset" on
page 17 for procedure.
• Attempt to add device back to smart
devices network.
If cycling power or factory
reset does not resolve issue
then replace the SAQM.
Automatically clears when
the system detects that the
issue no longer exists.