User Guide

506920−01 09/12
Page 38
Table 3. Adjustable Parameters Table (Installer)
Parameter Name: Installer entryIncrementParameter Value SettingDefault
Lock in 2nd stage HP by Outdoor Temp Off Off, 40ºF (4ºC), 45ºF (7ºC), 50ºF (10ºC), 55ºF (13ºC)
Balance Point Control Disabled Enabled, Disabled
Humiditrol Comfort Adjust Maximum Maximum, Midpoint, Minimum Overcooling
High Balance Point 50ºF −17ºF to 75ºF 1ºF
Low Balance Point Control 25ºF −20ºF to 72ºF 1ºF
Defrost Target Discharge Temp 55ºF 50ºF to 60ºF 1ºF
Dehumidification Control Mode Display Only
Display Only, Basic, Precision (only available when
NO dehumidifier is installed)
Humidification Control Mode Display Only
Display Only, Basic, Precision, Basic Dew Point Con-
trol, Precision Dew Point Control
Autochangeover Humidification Deadband 5% 5% to 10% 1%
Max Humidification Setpoint 45% 15% to 45% 1%
Min Dehumidification Setpoint 40% 40% to 60% 1%
Max Dehumidification Setpoint 40% 40% to 60% 1%
OK/Humid Boundary 50% 45% to 60% 1%
Outdoor Temperature Reading Calibration 0 −10ºF to 10ºF 1%
OUTDOOR EQUIPMENT (Go to EQUIPMENT button and scroll to HEAT PUMP or AIR CONDITIONER.)
Equipment Name (HP & AC) Outdoor Unit (keyboard input screen = up to 35 characters in string)
Compressor Short Cycle Delay (HP and AC) 300 Seconds 60 to 300 Seconds 60 Sec
Compressor Shift Delay On/Off (HP only) On On, Off
Defrost Termination Temp (HP only) 50ºF 50ºF to 100ºF 10ºF
table continued on next page