User Guide
506920−01 09/12
Page 36
Load−tracking Variable Capacity FAQs
(SLP98V only)
What is Load−tracking Variable Capacity? When an SLP98 Furnace is
connected to an icomfort Wi−Fi thermostat, the thermostat takes complete
charge of the variable capacity staging of the furnace. Load−tracking Vari-
able Capacity is only available with icomfort Wi−Fi thermostats.
How is Load−tracking Variable Capacity different from Variable Ca-
pacity? Load−tracking Variable Capacity will smoothly track the load (sensi-
ble temperature changes) up and down and adjust the furnace heating rate
both ways. Variable capacity only tracks the load upward (rising tempera-
ture). Variable capacity uses the thermostats stage differentials but not
stage timers. LVC disregards both stage differentials and stage timers.
What makes Load−tracking Variable Capacity work? With icomfort
Load−tracking Variable Capacity, the thermostat uses a Proportional Integral
Algorithm (PIA) to control firing rates of the furnace. The algorithm in the
Load−tracking Variable Capacity provides much more precise control over
the furnace than the Variable Capacity algorithm.
Interesting points about the Proportional Integral Algorithm
(PIA):
The further temperature is from the current set point, the higher PIA
sets the heating rate.
The longer away from a programmed set point, the higher the heating
rate.
If needed, PIA will turn heating on and off in short cycles when there
is a heat demand that is lower than the lowest the furnace can provide.
If the heat demand is higher than the minimum the furnace can provide,
the furnace will run without shutting off.
As the room temperature rises nearer the set point, the heating rate will
decrease.
As the room temperature falls further away from the set point, the heat-
ing rate will increase.
The stage differentials have no effect when running the PIA.
The second stage timers have no effect when running the PIA.










