Product Overview
Table Of Contents
- ICOMFORT® S30 THERMOSTAT
- BASIC INFOMATION
- INSTALLER SETTINGS
- USER SETTINGS
- ACCOUNT SCREEN
- ADVANCED SETTINGS (INSTALLER SETTINGS)
- AWAY SCREEN
- AWAY SETTINGS SCREEN
- COOL MENU SCREEN
- DISPLAY SCREEN
- EDIT SCHEDULES SCREEN
- FAN SCREEN
- FEELS LIKE SCREEN
- GENERAL SCREEN
- HEAT/COOL SCREEN
- HEAT MENU SCREEN
- HOME INFO SCREEN
- HOME SCREEN (Thermostat ON)
- HUMIDITY SCREEN (Humidity Control)
- IHARMONY ZONING SCREEN (if equipped)
- MENU SCREEN
- MODES/SCHEDULES SCREEN
- NAME SCREEN
- NOTIFICATIONS (REMINDERS) SCREEN
- PUREAIR™ S PERFORMANCE SCREEN
- SCHEDULE HOLD SCREEN
- SCHEDULES SCREEN
- SETTINGS SCREEN
- VENTILATION SCREEN (Fresh Air Damper/HRV/ERV)
- WEATHER FORECAST SCREEN
- WI-FI SCREEN
- ZONING SCREEN
- REVISIONS
iComfort
®
S30 Ultra Smart Thermostat / Page 35
INSTALLER SETTINGS
FRESH AIR DAMPER / HRV / ERV
Ventilation Control Mode Fresh Air
Damper
1 Stage
HRV
2 Stage
HRV
1 Stage
ERV
2 Stage
ERV
Timed
Ventilation Minutes Per Hour
(0 to 60 min., default is 20 min.)
X X X X X
Ventilation Rate
(20 to 500 cfm, default is 130 cfm)
- - - X - - - X - - -
Ventilation Rate for Low Speed
(10 to 200 cfm, default is 50 cfm)
- - - - - - X - - - X
Ventilation Rate for High Speed
(20 to 500 cfm, default is 130 cfm)
- - - - - - X - - - X
Ventilation High Outdoor Temperature Limit
(60 to 115°F, default is 100°F)
X X X X X
Ventilation Low Outdoor Temperature Limit
(–20 to 55°F, default is 0°F)
X X X X X
Ventilation High Outdoor Dew Point Limit
(45 to 80°F, default is 55°F)
X X X X X
ASHRAE (62.2)
Ventilation Rate
(20 to 500 cfm, default is 130 cfm)
- - - X - - - X - - -
Ventilation Rate for Low Speed
(10 to 200 cfm, default is 50 cfm)
- - - - - - X - - - X
Ventilation Rate for High Speed
(20 to 500 cfm, default is 130 cfm)
- - - - - - X - - - X
ASHRAE Compliance Check NO YES YES YES YES
ASHRAE Inltration Credit
(0 to 200 cfm, default is 0 cfm)
X X X X X
ASHRAE House Floor Area Serviced by this Ventilator X X X X X
ASHRAE Number of Bedrooms X X X X X
Ventilation Outdoor Condition Override - Enabled
Ventilation High Outdoor Temperature Limit
(60 to 115°F, default is 100°F)
X X X X X
Ventilation Low Outdoor Temperature Limit
(–20 to 55°F, default is 0°F)
X X X X X
Ventilation High Outdoor Dew Point Limit
(45 to 80°F, default is 55°F)
X X X X X
FEATURES