Product Overview
Table Of Contents
- ICOMFORT® S30 THERMOSTAT
- BASIC INFOMATION
- INSTALLER SETTINGS
- USER SETTINGS
- ACCOUNT SCREEN
- ADVANCED SETTINGS (INSTALLER SETTINGS)
- AWAY SCREEN
- AWAY SETTINGS SCREEN
- COOL MENU SCREEN
- DISPLAY SCREEN
- EDIT SCHEDULES SCREEN
- FAN SCREEN
- FEELS LIKE SCREEN
- GENERAL SCREEN
- HEAT/COOL SCREEN
- HEAT MENU SCREEN
- HOME INFO SCREEN
- HOME SCREEN (Thermostat ON)
- HUMIDITY SCREEN (Humidity Control)
- IHARMONY ZONING SCREEN (if equipped)
- MENU SCREEN
- MODES/SCHEDULES SCREEN
- NAME SCREEN
- NOTIFICATIONS (REMINDERS) SCREEN
- PUREAIR™ S PERFORMANCE SCREEN
- SCHEDULE HOLD SCREEN
- SCHEDULES SCREEN
- SETTINGS SCREEN
- VENTILATION SCREEN (Fresh Air Damper/HRV/ERV)
- WEATHER FORECAST SCREEN
- WI-FI SCREEN
- ZONING SCREEN
- REVISIONS
iComfort
®
S30 Ultra Smart Thermostat / Page 28
INSTALLER SETTINGS
EQUIPMENT (continued)
Smart Hub (continued)
(Adjust Settings)
• Temperature Control Mode (for Perfect Temp) (Normal,
Comfort)
Normal - Perfect Temp (single setpoint) is off.
Comfort - Perfect Temp (single setpoint) is on.
• Wall Insulation (poor, average, good) (default is good)
• Single Setpoint Mode (Enabled/Disabled)
Single Setpoint Mode is the same as Perfect Temp on the
User Screen (Heat & Cool). For non-zoning systems only.
Allows homeowner to set only one temperature setpoint
for heating and cooling.
• SSP Heating Cancel Coast Increment Slope
(0.0 to 0.75°F, default is 0.25°F)
• SSP Heating Cancel Coast Decrement Slope
(0.25 to 2.0°F, default is 0.5°F)
• SSP Cooling Cancel Counter Increment Slope
(–0.75 to 0.0°F, default is –0.25°F)
• SSP Cooling Cancel Counter Decrement Slope
(–2.0 to –0.25°F, default is –0.5°F)
• SSP Heating Lockout Outdoor Temp
(50.0 to 80.0°F, default is 70°F)
• SSP Cooling Lockout Outdoor Temp
(30.0 to 60.0°F, default is 40°F)
• Auto Changeover – Temp Deadband (3 to 9°F,
default is 3°F)
• Max. Heat Setpoint (40 to 90°F, default is 90°F)
• Min. Cool Setpoint (60 to 99°F, default is 60°F)
• Heat Cool Stages Locked In (Enabled/Disabled)
• 1st Stage Differential (0.5 to 3.0°F, default is 1.0°F)
• 2nd through 6th Stage Differential (0.5 to 8.0°F, default
is 0.5°F)
• Staged Delay Timers (Enabled/Disabled)
• 2nd through 6th Stage Delay (5 to 120 min. in 5 min.
increments, default is 20 min.)
Number of heating stages shown depends on equipment
installed. Electric heat is staged at every 2 elements.
• Lock In 2nd Stage HP by Outdoor Temp (off, 40°F
(4°C), 45°C (7°C), 50°F (10°C), 55°F (13°C)
XP21
• Balance Point Control (Enabled/Disabled)
• High Balance Point (–17 to 75°F, default is 50°F)
• Low Balance Point (–20 to 72°F, default is 25°F)
Heat Pump
• Min Dehumidication Setpoint (40 to 60°F, default is 40°F)
• Humiditrol Comfort Adjust (Maximum, Midpoint or
Minimum Overcooling)
Humiditrol
• Humidication Control Mode (Display Only, Precision,
Precision Dew Point Control, Basic, Basic Dew Point
Control)
• Dew Point Adjustment (–15 to 15°F, default is 0)
• Max. Humidication Setpoint (15 to 45% RH, default is
45%)
• Auto Changeover Humidication Deadband (5 to 10%
RH, default is 5%)
Humidier
• Outdoor Temperature Reading Calibration (–10 to 10°F,
default is 0)
• Auto Dehumidication Overcooling Threshold (0 to 10°F,
default is 4)
• Severe Weather Protection (enabled/disabled)
• Heat Alert Temperature (80 to 100°F, default is 90°F)
• Freezing Alert Temperature (30 to 50°F, default is 40°F)
• Zoning Gas Heating DAT Cooldown target (80 to 90°F,
default is 85°F)
• Zoning Anticipated Discharge Air Temperature
Adjustment (0 to 120 seconds, default is 60 seconds)
• Zoning Target Supply Air Temp for Cooling (40 to 60°F,
default is 45°F)
• Zoning Target Supply Air Temp for Gas/Electric
Heating (100 to 130°F, default is 110°F)
• Zoning Target Supply Air Temp for HP Heating (85 to
110°F, default is 90°F)
• Zoning Supply Air Temp Limit for Cooling (35 to 45°F,
default is 40°F)
• Zoning Supply Air Temp Limit for Gas/Electric Heating
(140 to 160°F, default is 140°F)
Zoning
• Humiditrol and Auxiliary Dehumidier Minimum
Runtime (5 to 30 min., default is 15 min.)
Humiditrol
• HP Heating Lockout Time (60 to 240 min., default is
120 min.)
D. Fuel
• Zoning Minimum Zone Run Time (90 to 600 sec.,
default is 120 sec.)
• Zone 1 through 4 First Stage Differential (0.5 to 3.0°F,
default is 1.0°F)
Zoning