Product Overview

iComfort
®
S30 Ultra Smart Thermostat / Page 28
INSTALLER SETTINGS
EQUIPMENT (continued)
Smart Hub (continued)
(Adjust Settings)
Temperature Control Mode (for Perfect Temp) (Normal,
Comfort)
Normal - Perfect Temp (single setpoint) is off.
Comfort - Perfect Temp (single setpoint) is on.
Wall Insulation (poor, average, good) (default is good)
Single Setpoint Mode (Enabled/Disabled)
Single Setpoint Mode is the same as Perfect Temp on the
User Screen (Heat & Cool). For non-zoning systems only.
Allows homeowner to set only one temperature setpoint
for heating and cooling.
SSP Heating Cancel Coast Increment Slope
(0.0 to 0.75°F, default is 0.25°F)
SSP Heating Cancel Coast Decrement Slope
(0.25 to 2.0°F, default is 0.5°F)
SSP Cooling Cancel Counter Increment Slope
(–0.75 to 0.0°F, default is –0.25°F)
SSP Cooling Cancel Counter Decrement Slope
(–2.0 to –0.25°F, default is –0.5°F)
SSP Heating Lockout Outdoor Temp
(50.0 to 80.0°F, default is 70°F)
SSP Cooling Lockout Outdoor Temp
(30.0 to 60.0°F, default is 40°F)
Auto Changeover – Temp Deadband (3 to 9°F,
default is 3°F)
Max. Heat Setpoint (40 to 90°F, default is 90°F)
Min. Cool Setpoint (60 to 99°F, default is 60°F)
Heat Cool Stages Locked In (Enabled/Disabled)
1st Stage Differential (0.5 to 3.0°F, default is 1.0°F)
2nd through 6th Stage Differential (0.5 to 8.0°F, default
is 0.5°F)
Staged Delay Timers (Enabled/Disabled)
2nd through 6th Stage Delay (5 to 120 min. in 5 min.
increments, default is 20 min.)
Number of heating stages shown depends on equipment
installed. Electric heat is staged at every 2 elements.
Lock In 2nd Stage HP by Outdoor Temp (off, 40°F
(4°C), 45°C (7°C), 50°F (10°C), 55°F (13°C)
XP21
Balance Point Control (Enabled/Disabled)
High Balance Point (–17 to 75°F, default is 50°F)
Low Balance Point (–20 to 72°F, default is 25°F)
Heat Pump
Min Dehumidication Setpoint (40 to 60°F, default is 40°F)
Humiditrol Comfort Adjust (Maximum, Midpoint or
Minimum Overcooling)
Humiditrol
Humidication Control Mode (Display Only, Precision,
Precision Dew Point Control, Basic, Basic Dew Point
Control)
Dew Point Adjustment (–15 to 15°F, default is 0)
Max. Humidication Setpoint (15 to 45% RH, default is
45%)
Auto Changeover Humidication Deadband (5 to 10%
RH, default is 5%)
Humidier
Outdoor Temperature Reading Calibration (–10 to 10°F,
default is 0)
Auto Dehumidication Overcooling Threshold (0 to 10°F,
default is 4)
Severe Weather Protection (enabled/disabled)
Heat Alert Temperature (80 to 100°F, default is 90°F)
Freezing Alert Temperature (30 to 50°F, default is 40°F)
Zoning Gas Heating DAT Cooldown target (80 to 90°F,
default is 85°F)
Zoning Anticipated Discharge Air Temperature
Adjustment (0 to 120 seconds, default is 60 seconds)
Zoning Target Supply Air Temp for Cooling (40 to 60°F,
default is 45°F)
Zoning Target Supply Air Temp for Gas/Electric
Heating (100 to 130°F, default is 110°F)
Zoning Target Supply Air Temp for HP Heating (85 to
110°F, default is 90°F)
Zoning Supply Air Temp Limit for Cooling (35 to 45°F,
default is 40°F)
Zoning Supply Air Temp Limit for Gas/Electric Heating
(140 to 160°F, default is 140°F)
Zoning
Humiditrol and Auxiliary Dehumidier Minimum
Runtime (5 to 30 min., default is 15 min.)
Humiditrol
HP Heating Lockout Time (60 to 240 min., default is
120 min.)
D. Fuel
Zoning Minimum Zone Run Time (90 to 600 sec.,
default is 120 sec.)
Zone 1 through 4 First Stage Differential (0.5 to 3.0°F,
default is 1.0°F)
Zoning
FEATURES