Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notications
Component or System Operational State and Troubleshooting Tip How to clear alert code
65541
Information
Only-Dealer
Download Failed
• Download for rmware failed.
• Typically the thermostat will send a command to the unknown device and place it in a soft
disable state.
The Lennox communicating control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines
on seven-segment display.
• On the damper control module, the green LED will blink three seconds on and one second off.
• On the equipment interface module, the green LED will blink three seconds on and one second
off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear
the soft disable state then replace control.
Not applicable.
65542
Information
Only-Dealer
Update Failed
• Has verication failed. Update failed.
• Solid blue LED will appear on mag-mount if powered. Only on versions with mag-mount.
• Blinking blue LED will appear if not communicating with smart hub. Only on versions with mag-
mount.
• Typically the thermostat will send a command to the unknown device and place it in a soft
disable state.
The Lennox communicating control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines
on seven-segment display.
• On the damper control module, the green LED will blink three seconds on and one second off.
• On the equipment interface module, the green LED will blink three seconds on and one second
off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear
the soft disable state then replace control.
Not applicable.
Automatically clears once is detected
for two seconds.
65543
Information
Only-Dealer
Firmware
Updated
• When new rmware has been successfully updated to the thermostat.
• Typically the thermostat will send a command to the unknown device and place it in a soft
disable state.
The Lennox communicating control with the soft disable state will indicate so as follows:
• On air handler, furnace and outdoor controls, the state is displayed by double horizontal lines
on seven-segment display.
• On the damper control module, the green LED will ash 3 seconds on and 1 second off.
• On the equipment interface module, the green LED will ash 3 seconds on and 1 second off.
Cycling power to the soft disabled control may clear the condition. If cycling power does not clear
the soft disable state then replace control.
Clears automatically after
successfully update.