Table 19. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notications
Component or System Operational State and Troubleshooting Tip How to clear alert code
430 26
Service
Soon/Service
Urgent
OD Inverter
Compressor
Startup Fail
Compressor start-up failure.
If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
Anti-short cycle is initiated.
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical
condition.
Inverter LEDs will ash code 26.
Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter ash code 26.
The sequence is:
Red LED: Two Flashes
Green LED: Six Flashes
NOTE: Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
Check refrigerant
Replace outdoor control board
Replace inverter.
To clear, disconnect power to outdoor
unit and restart.
431 27
Service
Soon/Service
Urgent
OD Inverter PFC
Fault
The inverter has detected a PFC circuit over-current condition.
Error occurs when PFC detects an over current condition of 100A peak.
If condition is detected, outdoor unit will stop (compressor and fan) – moderate condition.
Anti-short cycle timer is initiated.
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – critical
condition.
Inverter LEDs will ash code 27.
Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter ash code 27.
The sequence is:
Red LED: Two Flashes
Green LED: Seven Flashes
NOTE: Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
To clear, disconnect power to outdoor
unit and restart.