Product Overview
Table Of Contents
ComfortSense
®
7500 Commercial Touchscreen Thermostat / Page 9
FEATURES
INSTALLER SETTINGS (CONTINUED)
INSTALLER SETTINGS SCREEN (continued)
SSR (Smooth Setback Recovery) Stage 2 Lockout
• Enable (default) or Disable
• 20 min. (default), adjustable (20 to 120 minutes) in 10
minute increments
Contractor Information
• Name
• Address
•
• Email
• Website
• Number
Use the keyboard tool to input installer information
(maximum 30 characters).
TemperatureOset
•
temperature ± 5°F
HumidityOset
• 0% (default), adjustable (-10 to 10%)
Stage Delay Timer
•
Stage1Dierential
• 1.0°F (default), adjustable (0.5 to 8.0°F)
Stage2Dierential
• 1.0°F (default), adjustable (0.5 to 8.0°F)
Stage 2 Delay
• 20 min. (default), adjustable (5 to 120 minutes) in 10
minute increments
Stage3Dierential
• 0.5°F (default), adjustable (0.5 to 8.0°F)
Stage 3 Delay
• 20 min. (default), adjustable (5 to 120 minutes) in 10
minute increments
Stage4Dierential
• 0.5°F (default), adjustable (0.5 to 8.0°F)
Stage 4 Delay
• 20 min. (default), adjustable (5 to 120 minutes) in 10
minute increments
H/C Stages Locked In
•
separately
Stage 2 HP Lock Temp
•
compressor) applications, adjustable (-45 to 75°F)
Compressor Protect
•
Humidity Setting
• Dehumidify
• Normal, Max, Humiditrol (Min / Mid / Max),
Dehumidify Settings
normal setting is recommended for moderate climates.
max setting is recommended for humid climates. Operates
only. May cool beyond desired setpoint by 2 degrees.
rtu/auxiliarydehumidier setting is used with Landmark
®
Humiditrol (if equipped).
NOTE - Humiditrol settings are only available with optional
remote Outdoor Temperature Sensor.
Custom Reminder
• Two custom reminders
•
message (up to 20 alphanumeric characters)
Reset Setting
• Restores thermostat to original factory settings
Energy Saving Default
•
®
• OCC1 - 6 AM, 70°F Heat, 78°F Cool
•
•
•
System Test Mode
Installer run tests to check all cooling, heating,
signals between thermostat and unit are being sent and
received.
Test Outputs
• Y1 (1st stage cooling)
• Y2 (2nd stage cooling)
• W1 (1st stage heating)
• W2 (2nd stage heating)
• G (Fan)
• ECO (economizer)
•
• OB (reversing valve)
Touching the OFF button next to the test will change the
status to ON and will enable the relay for that terminal.
Touching again will turn the relay OFF.