Product Overview

ComfortSense
®
7500 Commercial Touchscreen Thermostat / Page 8
FEATURES
INSTALLER SETTINGS
From the Home Screen, touch Menu. Touch and hold
Settings to access the Installer Settings Screen.
System Setup
Sensor Setting
Residual Cool


Dead Band
Smooth Set Recovery
SSR (Smooth Setback Recovery) Stage 2 Lock Out
Contractor Information
󰀨
󰀨
Stage Delay Timer
󰀨
󰀨
Stage 2 Delay
󰀨
Stage 3 Delay
󰀨
Stage 4 Delay
H/C Stages Locked In


Humidity Setting
Custom Reminder
Reset Setting
Energy Saving Default
System Test Mode
INSTALLER SETTINGS SCREEN
Scroll down to see all selections available on the screen.
System Setup
Compressor Setting


Compressor Stage, 1 (default) or 2
Indoor Unit Setting
No Heat
Gas/Oil
Electric
Indoor Heat Stage, 1 (default) or 2
Sensor Setting
Outdoor Sensor
Outdoor
Discharge
No (default)
Indoor Sensor
Remote 10K
Remote 20K
Internal (default)
Up to nine indoor (room) sensors may be connected in
series for averaging. Sensors are not furnished and must
be ordered separately.
Residual Cool
0 (default), 30, 60, 90, 120 seconds
Low Balance Point (Multi-Stage Heat Pump)
Enable or Disable (default)
25°F (default), adjustable -40°F to 25°F
High Balance Point (Multi-stage Heat Pump)
Enable or Disable (default)
50°F (default), adjustable 27°F to 75°F
Touch and hold Enable to access the Low or High Balance

Deadband
2°F (default), adjustable (3 to 9°F)
Smooth Setback Recovery
Enable or Disable (default)