Product Overview
Table Of Contents
ComfortSense
®
7500 Commercial Touchscreen Thermostat / Page 8
FEATURES
INSTALLER SETTINGS
From the Home Screen, touch Menu. Touch and hold
Settings to access the Installer Settings Screen.
• System Setup
• Sensor Setting
• Residual Cool
•
•
• Dead Band
• Smooth Set Recovery
• SSR (Smooth Setback Recovery) Stage 2 Lock Out
• Contractor Information
•
•
• Stage Delay Timer
•
•
• Stage 2 Delay
•
• Stage 3 Delay
•
• Stage 4 Delay
• H/C Stages Locked In
•
•
• Humidity Setting
• Custom Reminder
• Reset Setting
• Energy Saving Default
• System Test Mode
INSTALLER SETTINGS SCREEN
Scroll down to see all selections available on the screen.
System Setup
Compressor Setting
•
•
• Compressor Stage, 1 (default) or 2
Indoor Unit Setting
• No Heat
• Gas/Oil
• Electric
• Indoor Heat Stage, 1 (default) or 2
Sensor Setting
Outdoor Sensor
• Outdoor
• Discharge
• No (default)
Indoor Sensor
• Remote 10K
• Remote 20K
• Internal (default)
Up to nine indoor (room) sensors may be connected in
series for averaging. Sensors are not furnished and must
be ordered separately.
Residual Cool
• 0 (default), 30, 60, 90, 120 seconds
Low Balance Point (Multi-Stage Heat Pump)
• Enable or Disable (default)
• 25°F (default), adjustable -40°F to 25°F
High Balance Point (Multi-stage Heat Pump)
• Enable or Disable (default)
• 50°F (default), adjustable 27°F to 75°F
Touch and hold Enable to access the Low or High Balance
Deadband
• 2°F (default), adjustable (3 to 9°F)
Smooth Setback Recovery
• Enable or Disable (default)