Brochure
Table Of Contents
- ELECTRIC HEAT DATA FOR AIR HANDLERS
- CBA25UH-018 | SINGLE PHASE
- CBA25UH-024 | SINGLE PHASE
- CBA25UH-030 | SINGLE PHASE
- CBA25UH-036 | SINGLE PHASE
- CBA25UH-042 | SINGLE PHASE
- CBA25UH-048 | CBA25UH-060 | SINGLE PHASE
- CBA25UHV-018 | SINGLE PHASE
- CBA25UHV-024 | SINGLE PHASE
- CBA25UHV-030 | SINGLE PHASE
- CBA25UHV-036 | SINGLE PHASE
- CBA25UHV-042 | SINGLE PHASE
- CBA25UHV-048 | CBA25UHV-060 | SINGLE PHASE
- CBA27UHE-018 | SINGLE PHASE
- CBA27UHE-024 | SINGLE PHASE
- CBA27UHE-030 | SINGLE PHASE
- CBA27UHE-036 | SINGLE PHASE
- CBA27UHE-036 | THREE PHASE
- CBA27UHE-042 | SINGLE PHASE
- CBA27UHE-042 | THREE PHASE
- CBA27UHE-048 | SINGLE PHASE
- CBA27UHE-048 | THREE PHASE
- CBA27UHE-060 | SINGLE PHASE
- CBA27UHE-060 | THREE PHASE
- CBA38MV-018/024 | SINGLE PHASE
- CBA38MV-030 | SINGLE PHASE
- CBA38MV-036 | SINGLE PHASE
- CBA38MV-036 | THREE PHASE
- CBA38MV-042 | SINGLE PHASE
- CBA38MV-042 | THREE PHASE
- CBA38MV-048 AND CBA38MV-060 | SINGLE PHASE
- CBA38MV-048 AND CBA38MV-060 | THREE PHASE
- REVISIONS
Air Handler Electric Heat Data / Page 23
ELECTRIC HEAT DATA CBA38MV-018/024 | SINGLE PHASE
Model Number
No. of
Stages
Volts
Input
kW
Input
1
Btuh
Input
2
Blower
Motor
Full Load
Amps
3
Minimum
Circuit
Ampacity
5
Maximum
Overcurrent
Protection
4 kW
4 lbs.
ECB38-4 (16V86)
Terminal Block
ECB38-4CB (16V87)
30A Circuit breaker
1 208 3.0 10,250 3.9 23
4
25
220 3.4 11,450 4.0 24
4
25
230 3.7 12,550 4.0 25
4
25
240 4.0 13,650 4.0 26 30
5 kW
4 lbs.
ECB38-5 (16V88)
Terminal Block
ECB38-5CB (16V89)
35A Circuit breaker
1 208 3.8 12,800 4.0 28
4
30
220 4.2 14,300 4.0 29
4
30
230 4.6 15,700 4.0 30
4
30
240 5.0 17,100 4.0 31 35
6 kW
4 lbs.
ECB38-6 (16V90)
Terminal Block
ECB38-6CB (16V91)
40A Circuit breaker
1 208 4.5 15,400 4.0 32
4
35
220 5.0 17,100 4.0 33
4
35
230 5.5 18,800 4.0 35
4
35
240 6.0 20,500 4.0 36 40
8 kW
5 lbs.
ECB38-8 (16V92)
Terminal Block
ECB38-8CB (16V93)
50A Circuit breaker
2 208 6.0 20,500 4.0 41
4
45
220 6.7 22,900 4.0 43
4
45
230 7.3 25,100 4.0 45
4
45
240 8.0 27,300 4.0 47 50
9 kW
5 lbs.
ECB38-9CB (16V94)
60A Circuit breaker
2 208 6.8 23,100 4.0 46
4
50
220 7.6 25,800 4.0 48
4
50
230 8.3 28,200 4.0 50
4
50
240 9.0 30,700 4.0 52 60
NOTE - Circuit 1 Minimum Circuit Ampacity includes the Blower Motor Full Load Amps.
1
Electric heater capacity only - does not include additional blower motor heat capacity.
2
Amps shown are for blower motor only.
3
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F.
4
Bold indicates that the circuit breaker on “CB” circuit breaker models must be replaced with size shown. See table on Page 1.
5
HACR type circuit breaker or fuse.