Datasheet
Page 1/3
060228/16
LEM Components www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Current Transducer LTS 15-NP
For the electronic measurement of currents : DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal r.m.s. current 15 At
I
P
Primary current, measuring range 0 .. ± 48 At
Î
PDC
Overload capability 250 At
V
OUT
Analog output voltage @ I
P
2.5
±
(0.625·I
P
/I
PN
)V
I
P
= 0 2.5
1)
V
N
S
Number of secondary turns (± 0.1 %) 2000
R
L
Load resistance ≥ 2 kΩ
R
IM
Internal measuring resistance (± 0.5 %) 83.33 Ω
TCR
IM
Thermal drift of R
IM
< 50 ppm/K
V
C
Supply voltage (± 5 %) 5 V
I
C
Current consumption @ V
C
= 5 V Typ 28+
I
S
2)
+
(V
OUT
/R
L
)mA
Accuracy - Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25°C ± 0.2 %
Accuracy with R
IM
@ I
PN
, T
A
= 25°C ± 0.7 %
ε
L
Linearity error < 0.1 %
Typ Max
TCV
OUT
Thermal drift of V
OUT
@ I
P
= 0 - 10°C .. + 85°C 65 120 ppm/K
- 40°C .. - 10°C 170 ppm/K
TCε
G
Thermal drift of the gain - 40°C .. + 85°C 50
3)
ppm/K
V
OM
Residual voltage
@ I
P
= 0, after an overload of 3 x I
PN
± 0.5 mV
5 x I
PN
± 2.0 mV
10 x I
PN
± 2.0 mV
t
ra
Reaction time @ 10 % of I
PN
< 100 ns
t
r
Response time @ 90 % of I
PN
< 400 ns
di/dt di/dt accurately followed > 35 A/µs
f Frequency bandwidth (0 .. - 0.5 dB) DC .. 100 kHz
(- 0.5 .. 1 dB) DC .. 200 kHz
General data
T
A
Ambient operating temperature - 40 .. + 85 °C
T
S
Ambient storage temperature - 40 .. + 100 °C
m Mass 10 g
Standards EN 50178 : 1997
IEC 60950-1 : 2001
Notes :
1)
Absolute value @ T
A
= 25°C, 2.475 < V
OUT
< 2.525
2)
I
S
= I
P
/N
S
3)
Only due to TCR
IM
.
Features
• Closed loop (compensated) multi-
range current transducer using the
Hall effect
• Unipolar voltage supply
• Compact design for PCB mounting
• Insulated plastic case recognized
according to UL 94-V0
• Incorporated measuring resistance
• Extended measuring range.
Advantages
• Excellent accuracy
• Very good linearity
• Very low temperature drift
• Optimized response time
• Wide frequency bandwidth
• No insertion losses
• High immunity to external
interference
• Current overload capability.
Applications
• AC variable speed drives and servo
motor drives
• Static converters for DC motor drives
• Battery supplied applications
• Uninterruptible Power Supplies
(UPS)
• Switched Mode Power Supplies
(SMPS)
• Power supplies for welding
applications.
Application domain
• Industrial.
I
PN
=
15 At
Copyright protected.
16058