Current Transducer LF 305-S
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal current rms 300 A
I
PM
Primary current, measuring range 0 .. ± 500 A
R
M
Measuring resistance @ T
A
= 70°C T
A
= 85°C
R
M min
R
M max
R
M min
R
M max
with ± 12 V @ ± 300 A
max
0 37 0 35
 @ ± 500 A
max
0 10 0 8
with ± 15 V @ ± 300 A
max
0 56 0 54
 @ ± 500 A
max
0 21 0 19
with ± 20 V @ ± 300 A
max
0 88 0 86
 @ ± 500 A
max
0 40 0 38
I
SN
Secondary nominal current rms 150 mA
K
N
Conversion ratio 1 : 2000
V
C
Supply voltage (± 5 %) ± 12 .. 20 V
I
C
Current consumption 26 (@± 20V)+ I
S
mA
X
G
Overall accuracy @ I
PN
, T
A
= 25°C ± 0.5 %
Accuracy - Dynamic performance data
ε
L
Linearity error < 0.1 %
Typ Max
I
O
Offset current @ I
P
= 0, T
A
= 25°C ± 0.2 mA
I
OM
Magnetic offset current
1)
@ I
P
=0 and specied R
M
after an overload of 3 x I
PN
± 0.2 mA
I
OT
Temperature variation of I
O
- 40°C .. + 85°C ± 0.2 ± 0.7 mA
- 10°C .. + 70°C ± 0.1 ± 0.3 mA
t
ra
Reaction time to 10 % of I
PN
< 500 ns
t
r
Response time
2)
to 90 % of I
PN
step < 1 µs
di/dt di/dt accurately followed > 100 A/µs
BW Frequency bandwidth (- 1 dB) DC .. 100 kHz
T
A
Ambient operating temperature - 40 .. + 85 °C
General data
T
S
Ambient storage temperature - 40 .. + 85 °C
R
S
Secondary coil resistance @ T
A
= 70°C 30
T
A
= 85°C 32
m Mass 95 g
Standards EN 50178:1997
Notes:
1)
The result of the coercive eld of the magnetic circuit
2)
With a di/dt of 100 A/µs.
I
PN
= 300 A
Features
Closed loop (compensated)
current transducer using the Hall
effect
Isolated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domains
Industrial.