Datasheet

www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
page 1/3
080715/9
Current Transducer LF 1005-S
For the electronic measurement of currents: DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal current rms 1000 A
I
PM
Primary current, measuring range @ ± 24 V 0 .. ± 1500 A
R
M
Measuring resistance @ T
A
= 70°C T
A
= 85°C
R
M min
R
M max
R
M min
R
M max
with ± 15 V @ ± 1000 A
max
0 18 0 15
@ ± 1200 A
max
0 7 0 4
with ± 24 V @ ± 1000 A
max
5 60.5 10 57.5
@ ± 1500 A
max
5 24 10 21
I
SN
Secondary nominal current rms 200 mA
K
N
Conversion ratio 1 : 5000
V
C
Supply voltage (± 5 %) ± 15 .. 24 V
I
C
Current consumption (± 1 mA) 28 (@ ± 24 V) + I
S
mA
Accuracy - Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25°C ± 0.4 %
ε
L
Linearity error < 0.1 %
Typ Max
I
O
Offset current @ I
P
= 0, T
A
= 25°C ± 0.4 mA
I
OM
Magnetic offset current
@ I
P
= 0 and specified R
M
,
after an overload of 3 x I
PN
± 0.2 mA
I
OT
Temperature variation of I
O
- 10°C .. + 85°C ± 0.3 ± 0.5 mA
- 40°C .. - 10°C ± 0.8 mA
t
r
Response time
1)
to 90 % of I
PN
step < 1 µs
di/dt di/dt accurately followed > 100 A/µs
BW Frequency bandwidth (- 1 dB) DC .. 150 kHz
General data
T
A
Ambient operating temperature - 40 .. + 85 °C
T
S
Ambient storage temperature - 45 .. + 100 °C
R
S
Secondary coil resistance @ T
A
= 70°C 48
T
A
= 85°C 51
m Mass 550 g
Standards EN 50178: 1997
Note :
1)
With a di/dt of 100 A/µs.
Features
Closed loop (compensated) current
transducer using the Hall effect
Isolated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application Domain
Industrial.
I
PN
= 1000
A
16110

Summary of content (3 pages)