Datasheet
Page 2/3
15June2015/version 16 LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LA 55-P
Insulation coordination
U
d
Rms voltage for AC insulation test, 50 Hz/1 min 2.5 kV
Û
W
Impulse withstand voltage 1.2/50 µs 5.7 kV
Min
d
Cp
Creepage distance 5 mm
d
CI
Clearance 5 mm
CTI Comparative tracking index (group I) 600
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
● Over voltage category OV 3
● Pollution degree PD2
● Non-uniform eld
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
EN 50178 IEC 61010-1
d
Cp
, d
CI
, Û
W
Rated insulation voltage Nominal voltage
Basic insulation 300 V 300 V
Reinforced insulation
150 V
150 V