Datasheet

LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice.
www.lem.com
Page 1/3
090508/15
I
PN
= 200 A
Features
Closed loop (compensated)
current transducer using the Hall
effect
Printed circuit board mounting
Isolated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domain
Industrial.
Current Transducer LA 200-P
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
I
PN
Primary nominal current rms 200 A
I
PM
Primary current, measuring range 0 .. ± 300 A
R
M
Measuring resistance @ T
A
= 70°C T
A
= 85°C
R
M min
R
M max
R
M min
R
M max
with ± 12 V @ ± 200 A
max
0 30 0 26
@ ± 250 A
max
0 8 0 4
with ± 15 V @ ± 200 A
max
0 60 0 56
@ ± 300 A
max
0 12 0 8
I
SN
Secondary nominal current rms 100 mA
K
N
Conversion ratio 1 : 2000
V
C
Supply voltage (± 5 %) ± 12 .. 15 V
I
C
Current consumption 16 (@ ± 15 V) + I
S
mA
X Accuracy @ I
PN
, T
A
= 25°C @ ± 15 V (± 5 %) ± 0.40 %
Accuracy - Dynamic performance data
@ ± 12 .. 15 V (± 5 %) ± 0.65 %
ε
L
Linearity error < 0.15 %
Typ Max
I
O
Offset current @ I
P
= 0, T
A
= 25°C ± 0.20 mA
I
OM
Magnetic offset current
1)
@ I
P
= 0 and specied R
M
,
after an overload of 3 x I
PN
± 0.25 mA
I
OT
Temperature variation of I
O
0°C .. + 70°C ± 0.10 ± 0.25 mA
- 40°C .. + 85°C ± 0.15 ± 0.55 mA
t
ra
Reaction time to 10 % of I
PN
step < 500 ns
t
r
Response time
2)
3)
to 90 % of I
PN
step < 1 µs
di/dt di/dt accurately followed
3)
> 200 A/µs
BW Frequency bandwidth (- 1 dB) DC .. 100 kHz
T
A
Ambient operating temperature - 40 .. + 85 °C
General data
T
S
Ambient storage temperature - 40 .. + 90 °C
R
S
Secondary coil resistance @ T
A
= 70°C 76
 T
A
= 85°C 80
m Mass 40 g
Standards EN 50178: 1997
Notes:
1)
The result of the coercive eld of the magnetic circuit
2)
With a di/dt of 100 A/µs
3)
The primary conductor is best lling the through-hole and/or the return of
the primary conductor is above the top of the transducer.
16044