Datasheet

LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice.
www.lem.com
Page 3/3
090804/6
Dimensions HTR 50 to 500-SB (in mm. 1 mm = 0.0394 inch)
Bottom view
Front view
Mechanical characteristics
General tolerance ± 1 mm ●
Primary through hole Ø 21 mm ●
Fastening 2 holes Ø 3.2 ●
Distance between holes axes 50 x 36 mm
or 1 hole Ø 3.2 and
1 spigot Ø 2.5
Distance between hole and sigot axes 36 mm
Connection of secondary Molex 5046-04/AG ●
“Malting connector provided with the transducer“
Remarks
V ●
OUT
is positive when I
P
ows in the direction of the arrow.
The return busbar and primary conductor elbow must be ●
located at least at 2.5 x window length more far away
from the transducer case.
Temperature of the primary busbar cannot exceed 90°C. ●
Dynamic performances are best with a primary busbar ●
completely lling the primary aperture.
This is a standard model. For different versions (supply ●
voltages, different output, unidirectional measurements
...), please contact us.
Secondary terminals
Terminal 1 : Supply voltage + 12 .. 15 V
Terminal 2 : Supply voltage - 12 .. 15 V
Terminal 3 : Output
Terminal 4 : 0V
Remarks:
• Vout is positive when Ip flows in the direction of the arrow.
• The temperature of the primary busbar can not exceed 90°C
• The return busbar and primary conductor elbow must be
located at least at 2,5 x window length more far away from the
transducer case.
• Dynamic performances are the best with a primary busbar
completely filling the primary aperture.
• This is a standard model. For different versions (supply
voltages, different outputs, unidirectional measurements...),
please contact us.
Mechanical characteristics:
• General tolerance ± 1 mm
• Primary aperture ∅ 21 mm
• Fastening 2 holes ∅ 3.2
Distance between holes axes: 50 x 36 mm
or 1 x hole ∅ 3.2 and 1 spigot ∅ 2.5
Distance between hole and sigot axes : 36 mm
• Secondary connection: Molex 5046-04/AG
Dimensions HTR 50 to 500-SB ( in mm, 1 mm = 0.0394 inch )
Front view
Bottom view
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Secondary connections:
1: Supply voltage +12 .. 15 V
2: Supply voltage -12 .. 15 V
3: Output
4: 0V