Datasheet

LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice.
120323/14
www.lem.com
Page 2/3
Current Transducer HASS 50..600-S
T
A
Ambient operating temperature - 40 .. + 85 °C
T
S
Ambient storage temperature - 40 .. + 85 °C
m Mass 55 g
Standards EN 50178:1997
Isolation characteristics
V
b
Rated isolation voltage rms with following conditions
-Over voltage categoryⅢ
-Pollution degree 2
-Heterogeneous eld
V
d
Rms voltage for AC isolation test, 50 Hz, 1 min 3.3 kV
V
e
Partial discharge extinction voltage rms @ 10 pC > 1 kV
V
w
Impulse withstand voltage 1.2/50 µs 6 kV
dCp Creepage distance > 5.5 mm
dCl Clearance distance > 5.5 mm
CTI Comparative Tracking Index (Group I) > 600 V
Safety
This transducer must be used in electric/electronic equipment with respect
to applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
General data
EN50178
IEC61010-1
Singleinsulation
600V
600V
Reinforcedinsulation
300V
150V