Datasheet

Page 1/3
6August2013/version 3 LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice www.lem.com
F2.20.34.200.0 - F2.20.44.200.0
DC Current Transducer DK-B10
Split core transducer for the electronic measurement of DC current,
with galvanic separation between the primary circuit and the secondary
circuit. 0-10 V DC output voltage proportional to measured current.
Electrical data
Primary nominal current Output voltage Types RoHS since
I
PN
(At) V
OUT
(V DC) date code
50, 75, 100 0-10 DK 100 B10 August 2009
100, 150, 200 0-10 DK 200 B10 August 2009
U
C
Supply voltage 20-45 V DC
R
L
Minimum load resistance 50 kΩ
V
SL
Output voltage limitation 11.5 V DC
I
C
Maximum current consumption 100 mA
Accuracy - Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25 °C ± 2 % of FS
ε
L
Linearity error ± 0.75 % of I
PN
t
r
Step response time
1)
to 90 % of I
PN
< 100 ms
BW Frequency bandwidth DC Hz
General data
T
A
Ambient operating temperature (0-95%) RH) - 20 .. + 50 °C
T
S
Ambient storage temperature - 20 .. + 85 °C
m Mass 120 g
IPxx Protection degree IP 20
Sandards Safety IEC 61010-1: 2001
EMC
1)
IEC 61326-1: 2005
Note:
1)
For IEC 61000-4-3, IEC 61000-4-6 and IEC 61000-4-4
Criterion B: temporary impairment to operational behavior.
I
PN
= 50 .. 200 A
Features
DC measurement (magnitude
only)
Split core case
Three jumper selectable ranges
Industry standard 0-10 V DC
unipolar voltage output
Panel mounting
Insulating plastic case recognized
according to UL 94-V0
Advantages
Large aperture
Extended measuring range
High insulation between primary
and secondary circuits
Easy to mount, cut installation
costs
No insertion loss (voltage drop).
Applications
Battery banks
Load current monitoring
Charging current monitoring
Operation supervision
Power supplies
DC power or auxiliary loads
measurement
Electric heating elements
Faster response than
temperature transducers.
Application domain
Renewable Energies and
Power Supplies.

Summary of content (3 pages)