Datasheet

Mechanical characteristics
General tolerance ± 1 mm
Primary aperture 104 x 40 mm
Busbar fastening 1 hole 5.5 mm &
2 slots 5.5 x 30 mm
Panel mounting 4 holes 3.2 mm
Distance between hole axes 15 x 150 mm
Remarks
The return busbar and primary conductor elbow must be
located at a minimum distance of 2.5 x the window length
away from the transducer case.
The temperature of the primary busbar can not exceed
90°C.
Dynamic performances are the best with a primary busbar
completely filling the primary aperture.
This is a standard model. For different versions
(supply voltages, different outputs, bidirectional
measurements...), please contact us.
Ip
Is
OUT
+24VDC
GND
Ip
Is
OUT
+24VDC
GND
Dimensions AHR-B10 (in mm. 1 mm = 0.0394 inch)
Connections
Wires up to 2 mm
Female connector provided (screw terminals)
104
8
.
3
0
174
4
0
8
6
25
50.50
20
9.10
54.10
150
110
22. 28
5.5 0
35
55
3
1
5
3
7
8
.
3
0
20.34
15
2
5
.
6
0
(+)
(-)
24 VDC Power
(Controller, meter etc)
Load
(-)
(+)
Output Connector
1(Vcc) 2(NC) 3(Vout) 4(GND)
080116/7 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 4/4