User's Manual

10
transportation(damage of meter cover, hanger, seal, and LCD display, etc)
As the internal part of the electrical meter is composed by the delicate electronic components,
the meter should be carefully protected during the installation in order to avoid any damage.
Make sure that the power is cut off before the meter
installation, otherwise it will cause a threat to life. The fuse
should be disconnected and put it in a safe place to avoid the
accidental power-on.
C) Installation procedure
1 Select the proper position according to the meter dimensions, and indicate fixing points of
the meter on the installation panel.
2 Drill down holes on previously marked positions. (make sure that there’s no cable behind
before punching, avoid ruining the cable and threatening personal safety)
3 Open the meter terminal cover, and adjust the height of hanger.
4 Using the vertical installation method, the meter is hanging on the hanger screw, and fixed
on the bottom by two screws. Need to ensure that the 3 screws are completely banned, and the
meter is installed firmly, without shaking.
To ensure the installation stability, the diameter of hanger screw must be greater
than 11mm, and the diameter of bottom fixed screws must be greater than 7mm.
5 Cut the cable to the required length and use the wire stripper to uncover the cable. The
recommended bare metal length after stripping is at least 20mm for this series of products.
We insist on the recommended length of the stripped wire to ensure that
the bare metal part is long enough and can be fixed by two connection
screws at the same time. However the bare part should not exceed the