Specification Sheet
  GUIDE SPECIFICATIONS 
Project Name  Project No.  Date 
Project Location  16140-4  Wiring Devices 
resistant thermoplastic construction; automatic ground clip; extra-long mounting 
strap; Quickloop wire looping aid; tri-drive screws; side-access push wire release; 
side wire accepts #12 - #14 AWG solid, push wire accepts #14 AWG solid only; 
[light almond] [ivory] [white] [brown] color. 
E.  20A Straight Blade Tamper-Resistant Duplex Receptacles: 
1.  General: Receptacles comply with UL 498 and CSA C22.2 No. 42. Meets NEC
®
Tamper-Resistant requirements. UL listed; CSA compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A  Tamper-Resistant  Duplex  Receptacles:  Part  No. 
TR26352R[LA][I][W][BK][GRY];  rated  20 amps,  125 volts;  single-pole/3-way; 
high-impact  resistant  thermoplastic  construction;  automatic  ground  clip;  extra-
long  mounting  strap;  Quickloop  wire  looping  aid;  tri-drive  screws;  side-access 
push wire release; side wire accepts #12 - #14 AWG solid, push wire accepts 
#14 AWG solid only; [light almond] [ivory] [white] [black] [brown] [gray] color. 
2.3  GFCI RECEPTACLES 
A.  Specification Grade Self-Test GFCI Duplex Receptacles: 
1.  General:  Receptacles  comply  with  UL 498,  UL 943,  Federal  Specification 
WC596,  Standard  CSA C22.2  No.  42,  and  CSA C22.2  No.  144.  Conforms  to 
NEMA WD-1 and WD-6; cULus listed File Number E42190. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A TradeMaster/Specification Grade Self-Test Tamper-Resistant GFCI Duplex 
Receptacles:  Part  No.  1597TR[LA][I][W][--][BK][NI][AB][DB];  rated  15 amps, 
125 volts;  nylon  face,  body,  and  test/reset  buttons;  thermoplastic  tamper-
resistant shutter; terminals accept #14 - #10 AWG solid or stranded copper or 
copper-clad conductors; SafeLock
®
 Protection performs an automatic test every 
three seconds to insure that ground fault protection is active; auto-ground clip; 
indicator light; [light almond] [ivory] [white] [brown] [black] [nickel] [antique brass] 
[dark bronze] finish and color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A TradeMaster/Specification Grade Self-Test GFCI Duplex Receptacles: Part 
No.  1597[LA][I][W][--][BK][GRY][RED];  rated  15 amps,  125 volts;  nylon  face, 
body, and test/reset buttons; terminals accept #14 - #10 AWG solid or stranded 
copper or copper-clad conductors; SafeLock
®
 Protection performs an automatic 
test  every  three  seconds  to  insure  that  ground  fault  protection  is  active;  auto-
ground clip; indicator light; [light almond] [ivory] [white] [brown] [black] [gray] [red] 
color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A TradeMaster/Specification Grade Self-Test Audible Alarm Tamper-Resistant 
GFCI  Duplex  Receptacles:  Part  No.  1597TRA[LA][I][W][BK];  rated  15 amps, 
125 volts;  nylon  face,  body,  and  test/reset  buttons;  thermoplastic  tamper-
resistant shutter; terminals accept #14 - #10 AWG solid or stranded copper or 
copper-clad conductors; SafeLock
®
 Protection performs an automatic test every 