Specification Sheet
  GUIDE SPECIFICATIONS 
Project Name  Project No.  Date 
Project Location  16140-12  Wiring Devices 
copper-clad conductors; SafeLock
®
 Protection performs an automatic test every 
three seconds to insure that ground fault protection is active; auto-ground clip; 
indicator  light;  [light  almond]  [ivory]  [white]  [gray]  [red]  [orange]  color.  RoHS 
Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A Hospital  Grade Self-Test  Combination  Tamper-Resistant Night  Light/GFCI 
Duplex  Receptacles:  Part  No.  1597HGNTLTR[I][W][--][RED];  rated  15 amps, 
125 volts;  nylon  face,  body,  and  test/reset  buttons;  thermoplastic  tamper-
resistant shutter; terminals accept #14 - #10 AWG solid or stranded copper or 
copper-clad conductors; SafeLock
®
 Protection performs an automatic test every 
three seconds to insure that ground fault protection is  active; auto-ground clip; 
indicator  light;  Lexan
®
  nightlight  lens;  [ivory]  [white]  [brown]  [red]  color.  RoHS 
Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A Hospital  Grade Self-Test  Combination  Tamper-Resistant Night  Light/GFCI 
Duplex  Receptacles:  Part  No.  2097HGNTLTR[LA][I][W][GRY][RED];  rated 
20 amps,  125 volts;  nylon  face,  body,  and  test/reset  buttons;  thermoplastic 
tamper-resistant  shutter;  terminals  accept  #14  -  #10  AWG  solid  or  stranded 
copper or copper-clad conductors; SafeLock
®
 Protection performs an automatic 
test  every  three  seconds  to  insure  that  ground fault  protection  is  active;  auto-
ground  clip;  indicator  light;  Lexan
®
  nightlight  lens;  [light  almond]  [ivory]  [white] 
[gray] [red] color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A  Hospital  Grade  Self-Test  Audible  Alarm  Tamper-Resistant  GFCI  Duplex 
Receptacles: Part No. 1597HGTRA[LA][--][GRY]; rated 15 amps, 125 volts; nylon 
face,  body,  and  test/reset  buttons;  thermoplastic  tamper-resistant  shutter; 
terminals  accept  #14  -  #10  AWG  solid  or  stranded  copper  or  copper-clad 
conductors;  SafeLock
®
  Protection  performs  an  automatic  test  every  three 
seconds to insure that ground fault protection is active; auto-ground clip; audible 
alarm; [light almond] [brown] [gray] color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A  Hospital  Grade  Self-Test  Audible  Alarm  Tamper-Resistant  GFCI  Duplex 
Receptacles:  Part  No.  2097HGTRA[LA][I][W][RED];  rated  20 amps,  125 volts; 
nylon face, body, and test/reset buttons; thermoplastic tamper-resistant shutter; 
terminals  accept  #14  -  #10  AWG  solid  or  stranded  copper  or  copper-clad 
conductors;  SafeLock
®
  Protection  performs  an  automatic  test  every  three 
seconds to insure that ground fault protection is active; auto-ground clip; audible 
alarm; [light almond] [ivory] [white] [red] color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A NAFTA-Compliant Hospital Grade Self-Test Tamper-Resistant GFCI Duplex 
Receptacles: Part  No. 2097HGTRNA[LA][I][W][RED];  rated  20 amps,  125 volts; 
nylon face, body, and test/reset buttons; thermoplastic tamper-resistant shutter; 