Specification Sheet
  GUIDE SPECIFICATIONS 
Project Name  Project No.  Date 
Project Location  16140-11  Wiring Devices 
face,  body,  and  test/reset  buttons;  thermoplastic  tamper-resistant  shutter; 
terminals  accept  #14  -  #10  AWG  solid  or  stranded  copper  or  copper-clad 
conductors;  SafeLock
®
  Protection  performs  an  automatic  test  every  three 
seconds to insure that ground fault protection is active; auto-ground clip; indicator 
light;  [light  almond]  [ivory]  [white]  [brown]  [black]  [gray]  [red]  color.  RoHS 
Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A Hospital Grade Self-Test GFCI Tamper-Resistant Duplex Receptacles: Part 
No.  2097HGTR[LA][I][W][--][BK][GRY][RED];  rated  20 amps,  125 volts;  nylon 
face,  body,  and  test/reset  buttons;  thermoplastic  tamper-resistant  shutter; 
terminals  accept  #14  -  #10  AWG  solid  or  stranded  copper  or  copper-clad 
conductors;  SafeLock
®
  Protection  performs  an  automatic  test  every  three 
seconds to insure that ground fault protection is active; auto-ground clip; indicator 
light;  [light  almond]  [ivory]  [white]  [brown]  [black]  [gray]  [red]  color.  RoHS 
Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
15A  Hospital  Grade  Self-Test  GFCI  Duplex  Receptacles:  Part  No. 
1597HG[LA][I][W][BK][GRY][RED];  rated  15 amps,  125 volts;  nylon  face,  body, 
and test/reset buttons; terminals accept #14 - #10 AWG solid or stranded copper 
or  copper-clad  conductors;  SafeLock
®
  Protection  performs  an  automatic  test 
every three seconds to insure that ground fault protection is active; auto-ground 
clip; indicator light; [light almond] [ivory] [white] [black] [gray] [red] color. RoHS 
Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A  Hospital  Grade  Self-Test  GFCI  Duplex  Receptacles:  Part  No. 
2097HG[LA][I][W][--][BK][GRY][RED]; rated 20 amps, 125 volts; nylon face, body, 
and test/reset buttons; terminals accept #14 - #10 AWG solid or stranded copper 
or  copper-clad  conductors;  SafeLock
®
  Protection  performs  an  automatic  test 
every three seconds to insure that ground fault protection is active; auto-ground 
clip; indicator light; [light almond] [ivory] [white] [brown] [black] [gray] [red] color. 
RoHS Compliant. 
15A Hospital  Grade Self-Test GFCI  Isolated Ground Tamper-Resistant Duplex 
Receptacles:  Part  No.  1597IGHGTRO;  rated  15 amps,  125 volts;  nylon  face, 
body,  and  test/reset  buttons;  thermoplastic  tamper-resistant  shutter;  terminals 
accept  #14  -  #10  AWG  solid  or  stranded  copper  or  copper-clad  conductors; 
SafeLock
®
 Protection performs an automatic test every three seconds to insure 
that  ground  fault  protection  is  active;  auto-ground  clip;  indicator  light;  orange 
color. RoHS Compliant. 
Specifier Note: Retain one or more colors and delete the others in brackets after Part No. and 
from description. 
20A Hospital  Grade Self-Test GFCI  Isolated Ground  Tamper-Resistant Duplex 
Receptacles:  Part  No.  2097IGHGTR[LA][I][W][GRY][RED][O];  rated  20 amps, 
125 volts;  nylon  face,  body,  and  test/reset  buttons;  thermoplastic  tamper-
resistant shutter; terminals accept #14 - #10 AWG solid or stranded copper or 