Installation manual

41
KEOR LINE RT 1000, 1500, 2200, 3000 VA
EN
MODEL NUMBER
1000VA
(3 100 45)
1500VA
(3 100 46)
2200VA
(3 100 47)
3000VA
(3 100 48)
Battery Parameters
Type Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating 3x36x7 3x36x9 6x72x7 6x72x9
Backup Time
50% Charge >10’ >8’ >8’ >8’
Recharge Time
5 hours to 90% of rated capacity,
after full discharge into resistive load
Environmental
Operating Temperature +32°F to + 104°C (0°C to + 40°C)
Storage Temperature +5°F to + 104°F (-15°C to + 40°C)
Relative Humidity 0% to 95%90%, non-condensing
Operating Altitude Up to 10,000 ft. (3000m) at 95°F (35°C) without derating
Audible Noise
<40 dBA, internal fan(s) Off
<45 dBA, internal fan(s) On
Standard and certifications
Safety EN-62040-1
EMC EN-62040-2
Markage CE