Datasheet

84
AC 23 A according to BS EN 60947-3 and IEC 60947-3, AC 22 A for 125 A
Double break contacts
Visible contact indicator
isolating switches DX
3
-IS
16 to 125 A
Dimensions p. 103
Technical information opposite
Pack Cat. Nos.
Isolating switches
Grey handle
Can be equipped with 1 DX
3
signalling auxiliary (p. 58)
Lock in open and closed position with locking device
Cat. No. 4063 03 and Ø 5 mm padlock Cat. No. 4063 13
Label holder for circuit indentification
1P - 250 V±
Nominal rating In (A) Number of modules
10
4064 00 16 1
10
4064 01 20 1
10
4064 03 32 1
10
4064 11 40 1
10
4064 12 63 1
10
4064 23 100 1
2P - 400 V±
10
4064 31 16 1
10
4064 32 20 1
10
4064 34 32 1
5
4064 40 40 2
5
4064 41 63 2
5
4064 53 63 with red handle 2
5
4064 55 100 with red handle 2
5
4064 50 125 2
2P with indicator - 400 V±
Supplied with lamp
Do not accept auxiliaries
10
4064 36 20 1
10
4064 38 32 1
3P - 400 V±
5
4064 57 20 2
5
4064 59 32 2
1
4064 60 40 3
1
4064 61 63 3
1
4064 75 100 with red handle 3
1
4064 70 125 3
4P - 400 V±
5
4064 77 20 2
5
4064 79 32 2
1
4064 80 40 4
1
4064 81 63 4
1
4064 95 100 with red handle 4
1
4064 90 125 4
4064 814064 59
NEW
n DX
3
-IS isolating switches
Electrical characteristics
1 : test conditions according to IEC 60947-3
AC 22 A : combined motor/resistor breaking with frequent operations
Thermal rating (Ith)
16 - 40 A
0.5 module/pole
40 - 63 A
1 module/pole
100 - 125 A
1 module/pole
Terminals Cage Cage Cage
Connection
flexible
1.5 to 10 mm
2
1.5 to 16 mm
2
1.5 to 25 mm
2
1.5 to 35 mm
2
4 to 35 mm
2
4 to 50 mm
2
rigid
Insulation voltage (Hi)
500 V± 500 V± 500 V±
Impulse withstand voltage
(Uimp)
6 kV 6 kV 6 kV
Category of use
1
AC 22 A AC 22 A AC 22 A
Short time withstand
current (Icw)
750 A 2000 A 2500 A
Short-circuit making
capacity (Icm)
1500 A 3000 A 3700 A
No. of electrical operations 30000 20000 5000
Protection index IP 2X wired IP 2X wired IP 2X wired
Accessories
Padlocking
2
4063 03
Support for one Ø5 mm padlock for
DX
3
MCBs and RCDs or isolating switches
3
4063 13
Ø5 mm shackle type padlock
Sealable screw cover - 4 separable poles
2
4063 04
For DX
3
isolating switches, 1 module per pole
Insulating shields
For DX
3
isolating switches,
1 module per pole
1
4063 05
Pole insulating shield (set of 6)
a093505a
084_087 IND 2014 v1.indd 84 10/04/2014 14:25

Summary of content (1 pages)