Technical data

3. PREPARATION (continued)
- By face plate using 4 screws Ø 4 mm
Piercing of support material for diameter 60-70 mm using cylinder
saw or punch.
3.3 Connection to conductors
- Automatic terminal mechanisms
The stripping length required is 13 mm. The correct stripping length can
be checked against the gauge on the rear of the base. Terminal capa-
city is 1.5 mm
2
- 2.5 mm
2
(1 or 2 conductors).
- Screw terminal mechanisms
3.4 Connection to conduits
Type of conduits :
- IRL : formerly IRO, insulating rigid smooth
- ICA : insulating bendable corrugated
- ICTA : insulating, bendable, transversally elastic,
corrugated
- ICTL : insulating, bendable, transversally elastic,
smooth
Cables (examples) :
- rigid conductors : U - 1000R2V 3G2.5
- flexible conductors : H07 RN - F 3G2.5
Type of outlet glands : membrane flexible, 2 removable types.
- 1-outlet gland supplied on 1-gang box (top and bottom)
- 1-outlet gland supplied on 2 and 3-gang boxes (top)
- 2-outlet gland supplied on 2 and 3-gang boxes (bottom)
Technical sheet : F00335EN/00 Updated : 21/03/2007 Created : 21/03/2007
2/5
Plexo socket outlets 2 P + E
Franco-Belgian standard
3. PREPARATION (continued)
3.4 Connection to conduits (continued)
Also available as accessories :
- 695 96 1-outlet gland grey
- 695 99 2-outlet gland grey
- 696 46 1-outlet gland white
- 696 49 2-outlet gland white
3.5 Assembly
The front part (cover) is IP55 locked onto the box using the four 1/4 turn
screws.
The direction of rotation of each 1/4 turn screw is marked on the cover.
1/4
Cat. Nos. : 695 51/52/53 - 696 21/22
697 31 - 698 31/70
61
61
Ø 60-70 mm
Ø 16 - 25 mm

Ø 4 - Ø 15 mm Ø 16/20/25 mm
13 m m
}
Pillar terminals supplied open, with screws
backed off and locked
Min. capacity : 1 x 1.5 mm
2
Max. capacity : 3 x 2.5 mm
2
or 2 x 4 mm
2
Max. tightening torque : 0.8 N/m
Usable screwdrivers : flat blade 3.5-5 mm
or Philips No.1