Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
P167
(1)
Base Frequency 60.0 10.0 {Hz} 1500
V0112
P168
Fixed Boost 0.0 {%} 30.0
Note
P167 = rated motor frequency for standard applications
P168 default setting depends on drive rating
P169
Accel Boost 0.0 0.0 {%} 20.0 Accel Boost is only active during
acceleration
P170
Slip
Compensation
0.0 0.0 {%} 10.0 Increase P170 until the motor speed
no longer changes between no load
and full load conditions.
P171
(1)
Current Limit 200 30 {%} CLim
max
When the limit is reached, the
drive displays
CL, and either the
acceleration time increases or the
output frequency decreases.
Digital outputs can also indicate
when the limit is reached; see
P140, P142.
Refer to section 2.2 for CLim
max
P172
Current Limit
Reduction
0 0 Current Limit Reduction
Active - Normal response
In eld weakening, the Current Limit
is inversely proportional to the speed.
1 Current Limit Reduction Active
- Fast response
2 Current Limit Reduction
Disabled - Normal response
3 Current Limit Reduction
Disabled - Fast response
P173
Decel Override
Time
2.0 0.0 {s} 60.0 Maximum time before drive trips into
HF fault.
P174
DC Brake
Voltage
0.0 0.0 {%} 30.0 Setting is a percent of the nominal
DC bus voltage.
(1) The drive can only be restarted if the error message has been reset