User guide

relayoropen-collectoroutputwillde-energize,whichopensthestartcontactandstopsthedrive.Whenthe
signalisequaltoorgreaterthantheMINALARMsetting,therelayoropen-collectoroutputwillenergize,
which closes the start contact and starts the drive. The drive must be in REMOTE mode to use the MIN/
MAX function to start and stop the drive.
NOTE 2:WhenusingtheMINandMAXALARMfunctionsinopen-loopspeedmode(PIDisdisabled),
parameter 74 - PID FB must still be set to match the speed reference signal being used.
98 LANGUAGE (LANGUAGESELECTION)
The MICRO Series drive can support other languages with the addition of an optional LANGUAGE
EEPROMchipinstalledinsocketU11onthecontrolboardofthedrive.IftheEEPROMisnotpresent,
the default language will be ENGLISH. Also, this parameter is not affected when the parameters are reset
using Parameter 65 - PROGRAM. Therefore, if a language other than ENGLISH is selected, it will remain
in effect after a RESET.
99 FAULT HISTORY
The FAULT HISTORY stores the previous eight fault conditions that caused the drive to trip. The
information stored here is view-only, it cannot be altered. The FAULT HISTORY can be used to determine
if there is a pattern, or trend, to the faults, which may indicate a problem in the system. Refer to Section
19.0 - TROUBLESHOOTING for more information on faults.
TheFAULTHISTORYindicatesthenumberofthefault(number1isthemostrecentfault),thefault
message,andthestatusofthedriveatthetimeofthefault.Anexampleisshownbelow:
Intheexampleabove,thethirdfaultlogisbeingviewed,whichisanOVERLOADfaultthatoccurredwhile
the drive was in a RUN state.
76