User guide
70 PID MODE (PIDMODESELECT)
This parameter activates the PID function, and selects whether the PID control will be direct or reverse
acting. Refer to Section 19.0 - MICRO Series PID SET POINT CONTROL. The following options are
available:
OFF DisablesthePIDfunctiontoallow“standard”driveoperation.
NORMAL EnablesthePIDfunctionfordirectactingsystems.Anincreaseinthefeedbackvariable
will cause a decrease in motor speed.
REVERSE Enables the PID function for reverse acting systems. An increase in the feedback
variable will cause an increase in motor speed.
NOTE:TheREVERSEselectionisnotusedtocompensateforreverseactingfeedbackdevices.Ifareverse
actingfeedbackdeviceisused,programParameters75and76-FB@MINandFB@MAXasdescribed
in Section 19.1 - FEEDBACK DEVICES.
When PID is enabled, and the drive is in REMOTE and AUTO mode, the drive will operate in a CLOSED
LOOPfashion,respondingtothefeedbacksignalinordertomaintaintheprocesssetpoint.Inthiscase,
thesetpointreferencecanbea0-10VDCor4-20mAsignal,orthekeypad.TheSPEEDREFERENCE
SOURCEindicationintheCONTROLdisplaywillindicateVDC(0-10VDC),IDC(4-20mA),orAKB
(keypad),dependingonthesetpointreference.
When PID is enabled, and the drive is in LOCAL and AUTO mode, the drive will also operate in a
CLOSEDLOOPfashion.However,inthiscase,theonlysetpointreferenceavailableisthekeypad,and
the SPEED REFERENCE SOURCE indication in the CONTROL display will indicate AKB.
When PID is enabled, and the drive is in MANUAL and LOCAL or REMOTE mode, the drive will
operateinanOPENLOOPfashion,respondingdirectlytospeedcommandsfromthekeypadonly.The
SPEED REFERENCE SOURCE indication in the CONTROL display will indicate MKB.
When PID is disabled, the drive will operate in an OPEN LOOP mode, responding directly to speed
commandsfromeitherthekeypad(MANUALmode)orananaloginputsignalorpresetspeed(AUTO
mode).
74 PID FB (PIDFEEDBACKSOURCE)
Thisparameterselectstheterminaltobeusedforthefeedbacksignal,andcanbesettoTB-5AorTB-5B.
TB-5A is used for 0-10 VDC signals, and TB-5B is used for 4-20 mA signals.
NOTE: The MICRO Series has only one analog input of each type, so the same type of signal cannot be
usedforfeedbackandsetpointreference.Forexample,a4-20mAsignalfromatransducercouldnotbe
usedasafeedbacksignalifthesetpointisbeingcontrolledbya4-20mAsignalfromaPLC.
75 FB @ MIN (MINIMUMFEEDBACKVALUE)
This parameter should be set to the value of the process variable that corresponds to the minimum
transducerfeedbacksignal(0VDCor4mA).
76 FB @ MAX (MAXIMUMFEEDBACKVALUE)
This parameter should be set to the value of the process variable that corresponds to the maximum
transducerfeedbacksignal(10VDCor20mA).
74