65 PROGRAM (PROGRAMFACTORYDEFAULTS)
STOP(TB-1)andEXTERNALFAULT(TB-13D)circuitrymaybedisabledifparametersare
resettofactory defaults!The drive mustbe reprogrammedaftera RESETinorder toinsure
proper operation.
FAILURETODOSOMAYRESULTINDAMAGETOEQUIPMENTAND/ORINJURY
TOPERSONNEL!
This parameter is used to reset the programmable parameters back to the factory default settings. This
parameter has four possible settings:
MAINTAIN Maintain parameter settings as they are.
RESET60 Resetsparameterstofactorydefaultsfor60Hzbasefrequency.
RESET50 Resetsparameterstofactorydefaultsfor50Hzbasefrequency.
RSTHIGH Resetsparameterstofactorydefaultsfor650Hzbasefrequency.Thisoptionwillonly
appearifthedriveisequippedwiththeHighFrequencyOutputoption.
When a factory reset is performed, the following terminals are affected:
TB-1 will be disabled because Parameter 30 - CONTROL will default to LOCAL.
TB-13A, 13B, and 13C will be disabled because Parameters 47, 48, and 49 will default to NONE. If
TB-13C was set to RUN REVERSE, TB-12A will default to a momentary START contact.
TB-13D will default to a normally open EXTERNAL FAULT contact because Parameter 50 - TB13D EXT
will be reset to FAULT.
NOTE: This parameter will display RESET 60, RESET 50 or RST HIGH until a change is made to one
or more of the parameter settings. Once a parameter is changed, the display will change to MAINTAIN.
66 HISTORY (CLEARFAULTHISTORY)
This parameter is used to clear the previous faults in the FAULT HISTORY. When set to CLEAR and the
ENTERkeyispushed,thedisplaywillchangetoMAINTAIN,andtheFAULTHISTORYwilldisplay
NO FAULT for each of the eight fault histories.
69 LANGUAGE (LANGUAGESELECTION)
The MICRO Series drive can support other languages with the addition of an optional LANGUAGE
EEPROMchipinstalledinsocketU11onthecontrolboardofthedrive.IFtheEEPROMisnotpresent,
the default language will be ENGLISH. Also, this parameter is not affected when the parameters are reset
using Parameter 65 - PROGRAM. Therefore, if a language other than ENGLISH is selected, it will remain
in effect after a RESET.
73