User guide

49 TB13C (TB-13CINPUTFUNCTION)
If TB-13C is programmed for RUN REVERSE, TB-1 is disabled and CANNOT be used as a
STOPswitch!ThisistrueinLOCALandREMOTEmode.IncorrectuseofTB-1mayresult
indamagetoequipmentand/orinjurytopersonnel!
This parameter is used to select the function of terminal TB-13C. Closing TB- 13C to TB-2 activates the
TB-13C input function. The following functions can be selected.
NONE Disables the TB-13C function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input. The 0-10 VDC signal is wired
to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input. The 4-20 mA signal is wired to
TB-5B and TB-2.
SPEED#3 Selects PRESET SPEED #3 as the AUTO speed reference.
LOC SEL LOCAL SELECT - Selects LOCAL mode when Parameter 30 - CONTROL is set to
BOTH. Drive is in REMOTE mode if contact closure is not made.
RUNREV RUNREVERSE-Runinreversedirection.Requiresamaintainedcontactclosure-
close to RUN in reverse direction, open to STOP. This will cause TB-12A to function
asRUNFORWARD,alsorequiringamaintainedcontact.
STRTREV STARTREVERSE-Startinreversedirection.Requiresamomentarycontactclosure
to RUN in reverse direction. A momentary STOP contact must be wired between
TB-1 and TB-2. Setting this parameter to START REVERSE causes TB-12A to
functionasSTARTFORWARD,alsorequiringamomentarycontactclosuretoRUN
in forward direction.
68
WARNING