User guide

47 TB13A (TB-13AINPUTFUNCTION)
This parameter is used to select the function of terminal TB-13A. Closing TB-13A to TB-2 activates the
TB-13A input function.
The following functions can be selected:
NONE Disables the TB-13A function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input. The 0-10 VDC signal is
wired to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input. The 4-20 mA signal is wired to
TB-5B and TB-2.
SPEED#1 Selects PRESET SPEED #1 as the AUTO speed reference.
LOC SEL Selects LOCAL mode when Parameter 30 - CONTROL is set to BOTH. Drive is in
REMOTE mode if contact closure is not made.
DECFREQ Decrease frequency set point. Used with the MOP (motor operated pot) function.
Refer to Section 14.2.6 - SPEED REFERENCE SELECTION.
48 TB13B (TB-13BINPUTFUNCTION)
WhenoperatinginJOGmode,theSTOPkeyWILLNOTstopthedrive.Tostopthedrive,
the contact between TB-13B and TB-2 must be opened.
This parameter is used to select the function of terminal TB-13B. Closing TB-13B to TB-2 activates the
TB-13B function. The following functions can be selected:
NONE Disables the TB-13B function.
0-10VDC Selects 0-10 VDC as the AUTO speed reference input. The0-10 VDC signal is wired
to TB-5A and TB-2.
4-20 MA Selects 4-20 mA as the AUTO speed reference input. The 4-20 mA signal is wired to
TB-5B and TB-2.
SPEED#2 Selects PRESET SPEED #2 as the AUTO speed reference.
INCFREQ Increasefrequencysetpoint.UsedwiththeMOP(motoroperatedpot)function.Refer
to Section 14.2.6 - SPEED REFERENCE SELECTION.
JOGFWD Jogintheforwarddirection.ActiveonlywhendriveisSTOPPED.Thejogspeedis
set by Parameter 2 -SPEED#2.
JOGREV Jogin thereversedirection. Activeonly when driveis STOPPED.Thejog speedis
set by Parameter 2 - SPEED#2.
67
WARNING