User guide
41 AIN FLTR (ANALOGINPUTFILTER)
Thisparameteradjuststhefilterontheanaloginputterminals(TB-5AandTB-5B)toreducetheeffectof
anyelectricalnoisethatmaybepresentontheanaloginputsignals.ThisfilterworksinbothPIDmode
and standard speed control mode. It should be set to the lowest value that yields acceptable performance, as
setting it too high may cause the drive to react too slowly to signal changes.
42 TB10A OUT (TERMINALTB-10AOUTPUT)
TheanalogoutputsignalatTB-10Aisproportionaltotheoutputfrequencyofthedrive.Thisparameter
selects whether that signal is 0-10 VDC or 2-10 VDC. The 2-10 VDC signal can be converted to a 4-20
mA signal by connecting a resistor in series with the signal such that the total load resistance is 500 Ohms.
If set to NONE, the function is disabled.
NOTE:Thisoutputcannotbeusedwith“loop-powered”devicesthatderivepowerfroma4-20mAsignal.
43 @ TB10A (TERMINALTB-10ASCALING)
This parameter scales the analog output signal at TB-10A. This setting is the output frequency that is
indicated when the TB-10A output measures 10VDC.
Example:Thedriveispartofacontrolsystemthatrequiresa0-5VDCsignal(ratherthan0-10VDC)that
isproportionalto0-60Hzoutputfrequency.Theoutputsignalislinear,sosettingthisparameterto120
Hzwouldyield10VDCat120Hz,and5VDCat60Hz.
44 TB10B OUT (TERMINALTB-10BOUTPUT)
The analog output signal at TB-10B is proportional to the drive load. This parameter selects whether
that signal is 0-10 VDC or 2-10 VDC. The 2-10 VDC signal can be converted to a 4-20 mA signal by
connecting a resistor in series with the signal such that the total load resistance is 500 Ohms.
NOTE:Thisoutputcannotbeusedwith“loop-powered”devicesthatderivepowerfroma4-20mAsignal.
45 @ TB10B (TERMINALTB-10BSCALING)
ThisparameterscalestheanalogoutputsignalatTB-10B.Thissettingistheload(in%)thatisindicated
when the TB-10B output measures 10 VDC.
Example:Thedriveispartofacontrolsystemthatrequiresa0-10VDCsignaltoindicate0-150%drive
load. If this parameter were set to 150%, the drive would output 10 VDC at 150% load (and about 6.7
VDCat100%load).
NOTE: The output signal at TB-10B is affected by the setting of Parameter 34 - LOAD MLT.
66