-24-
Class I Area Classification Class II Area Classification
(Flammable Gases, Vapors or Mists) (Combustible Dusts)
Europe - ATEX Europe - ATEX
North America (Category G - Gases) North America (Category D - Dusts)
Division 1 Division 2 Division 1
Explosion TEFC &
Zone 1 Zone 2
Explosion Division2
Zone 21 Zone 22
Proof TENV
Flameproof Non-Sparking
Proof
Flameproof Non-Sparking
Group A
¬
Group A Group IIC, Category G
¬
Group IIC, Category G - - - -
Group B
¬
Group B Group IIC, Category G
¬
Group IIC, Category G - - - -
Group C Group C Group IIB, Category G Group IIB, Category G - - - -
Group D Group D Group IIA, Category G Group IIA, Category G - - - -
- - - - Group E
¬
- - -
- - - - Group F Group F
¬
Category D -
- - - - Group G Group G
¬
Category D -
Hazardous Duty Motor Area Classification Chart
- Group is not applicable to that Division or Zone, or is not defined.
¬
Group is not available from LEESON Electric or Lincoln Motors.