The first byte is the number of detections in the message. Because of the limitation
on a Modbus message length, a maximum of 40 detections will be returned.
NOTE: This maximum can be configured to a lower value using the Leddar
Configurator software (serial port configuration) or the Write Register
command described below.
Following the first byte, each detection has six bytes (refer to Table 26)
Table 26: Get detection messages (detection fields)
Offset
Length
Description
0
2
The distance (little-endian). Distance unit is defined by serial port
parameters
2
2
The amplitude times 64 [that is, amplitude = this field/64 (little-endian)]
4
1
3 bits are flags describing the measurement (all others are reserved):
Bit 0: Detection is valid (will always be set)
Bit 1: Detection was the result of object demerging
Bit 2: Reserved
Bit 3: Detection is saturated
5
1
Segment number
Trailing all the detections have 3 more fields (refer to Table 27).
Table 27: Get detection messages (trailing fields)
Offset
Length
Description
0
4
Timestamp of the acquisition (little-endian). The timestamp is expressed
as the number of milliseconds since the device was started.
4
1
Current light source power as a percentage of maximum.
5
2
Bit-field acquisition. Reserved
Read module data (function code 0x42)
Table 28 and Table 29 present the request and answer codes for reading data.
Table 28: Requests
Offset
Length
Description
0
4
Base address: 0x00000000 to 0x00FFFFFF