Instruction Manual
page www.signify.com6/9/2022 8
www.ledalite.com
!
ATTENTION: Install in accordance with local and national building and electric codes.
Daylight sensor
The light sensor measures the total amount of light in
a circular field of approximately 80% of the PIR
detection area. The following aspects should be
observed during installation:
• Minimum distance from the window ≥2ft (0.6m).
• Prevent light reflections from outside entering the
sensor (for example sunlight reflection on a car
hood) as this will lead to incorrect light regulation.
As a guideline the formula 0.72 x H can be used to
calculate the minimum distance between the window
and sensor whereby H is the height from the bottom
of the window to the sensor.
Occupancy Sensor Coverage:
Note: Longer dimension of detection area (Y1, Y2) is
parallel to longer dimension of the luminaire.
The detection area for the movement sensor can be
roughly divided into two parts:
• Minor movement (person moving ≤3ft/s or 0.9m/s).
• Major movement (person moving ≥3ft/s or 0.9m/s).
Photosensor spatial response
TruGroove Drywall Trim Installation Instructions
ID-23