Datasheet

U.I. Lapp
GmbH
DATA SHEET
UNITRONICBUS PB Yv 1 x 2 x 0,64
DB2170223
valid from: 29.11.2011
Originator: RAWE/PDC
approved: HAPF/PDC
Document: DB2170223 page 1 of 2
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10DE
Application
Fieldbus cable for the Siemens field network SIMATIC NET (acc. to DIN 19245 part 3 and EN 50170), for fieldbus system FIP
(Factory Instrumentation Protocol) as well as for high performance data networks with 150 Ohms nominal impedance. The
cable is designed for the system-defined transmission rates of 1.5 Mbit/s, 2.5 Mbit/s and 12 Mbit/s, the transmission
characteristics are conform to the system and guarantee a high operating security during data transmission.
Due to it´s double screening it is suitable for installation in electromagnetically demanding areas. The cable is intended for
permanent installation inside and outside as well as for underground burial. The outer sheath is unaffected by atmospheric
UV-radiation at above-ground installation.
Design
Conductor bare copper wire, nom. 0.64 mm Ø
Insulation skin-foam-skin PE, alternatively foam-skin, core Ø nom. 2.55 mm
Core identification code cores red similar to RAL 3000 and green similar to RAL 6018
Stranding 2 cores together with 2 fillers
Wrapping 1 layer plastic foil
Screening plastic-laminated aluminium foil, side with metal outwards, braid of tinned
copper wires, coverage nom. 85%
Outer sheath PVC, lead free, shore hardness A 77 ± 3, black similar to RAL 9005,
wall thickness nom. 1.8 mm, outer diameter: ca. 9.4 mm
Electrical properties at 20° C
Resistance (loop) max. 110 Ω/km
Insulation resistance min. 5 GΩxkm
Mutual capacitance ca. 28 nF/km
(at 800 Hz)
Inductance ca. 0.83 mH/km
(at 800 Hz)
Characteristic impedance 9.6 kHz: 270 Ω ± 27
38.4 kHz: 185 Ω ± 18.5
3 bis 20 Mhz: 150 Ω ± 15
Line attenuation 9.6 kHz: max. 0.25 dB/100 m
38.4 kHz: max. 0.4 dB/100 m
200 kHz: max. 0.9 dB/100 m
4 MHz: max. 2.2 dB/100 m
16 MHz: max. 4.2 dB/10 0m
Velocity of propagation nom. 81%
Transfer impedance up to 20 MHz max. 10 mΩ/m
Operating peak voltage 225 V (not for power purposes)
Test voltage U
eff.
core/core und
core/screen
1500 V