Datasheet

DATA SHEET
0162052
IEC compensating cable KN 5-022 L-CY 2x0,22
valid from :
01.12.2008
Originator: Frank Hörtnagl / PD-KL
Approved: Werner Körner / TE
Document: DB0162052EN page 1 of 1
All deviations from this specification are subject to explicit consent of U.I.LAPP GmbH. All rights reserved acc. to DIN 34.
No.: 0019/0408
Application
The compensating cable KN 5-022 L-CY 2 x 0,22 mis a PVC insulated cable which transmits the thermo-
electric voltage of NiCr/Ni thermocouples. It is for flexible use and fixed installation in dry and damp rooms. They
may only be installed outdoors with UV protection and in observation of the max. permitted temperature range.
The copper braiding screens the cable against electromagnetical interference.
Design
Conductor 0,22 mm² (7 x 0,20 mm)
Conductor material KCA alloying, accuracy class 2 according IEC 60584
Positive conductor: Fe (iron)
Negative conductor: CuNi (cupronickel)
Core insulation PVC compound
Core identification Positive conductor: green
Negative conductor: white
Core layering Cores twisted together
Inner sheath PVC compound, colour: green
Screening tinned copper braiding
Outer sheath PVC compound, colour: green
Electrical properties
Limiting deviation class 2 ± 100 µV (± 2,5 °C) / m easuring point temperature +900 °C
Mechanical and thermal properties
Temperature range occasional flexing: -5 °C up to +70 °C
Minimum bending radius occasional flexing: 15 x cable diameter
Flammability flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2