Data Sheet
U.I. Lapp 
GmbH 
DATA SHEET 
Multi-Standard SC 2.2
DB 4150100 
valid from: 2013-07-11 
Originator: KASC / PDC
approved: HAPF / PDC 
Document:  DB4150100EN  page 1 of 1 
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34. 
PD 0019/2.1_11.09EN 
Application 
These multi standard wiring cables SC2.2 are UL, CSA and HAR (VDE)* approved and are designed for use for control cabi-
net  wiring  as  well  as  for  installation  in  protective  tubes,  applicable  within  the  scope  of  the  UL-  or  Canadian  or  European 
standard specifications. They are especially qualified for wiring in industrial machines in accordance with NFPA 79. At room 
temperature they are widely resistant to oils. 
Application range:  HAR:  Wiring cable for internal wiring acc. to 
    DIN EN 50525-2-31 resp. VDE 0285-525-2-31 
  UL (MTW):  acc. to ANSI/NFPA 70 (National Electrical Code) 
  UL (AWM):  oil resistant wiring cable for internal wiring 
  CSA (TEW):  oil resistant wiring cable for internal wiring of devices 
Design 
Design / Approvals  H07V2-K ◄HAR► (*) acc. to DIN EN 50525-2-31 resp. VDE 0285-525-2-31 
  UL (MTW) acc. to UL 1063, File-No. E198296 
  UL (AWM) Style 10269 acc. to UL 758 
  CSA (TEW) acc. to C22.2 No. 127-09 
*For the dimensions 0.5; 0.75; 1.0; 16; 50; 70; 95; 120 mm² as well for the colours GN, YE and multi-coloured cores (except  
 for GN YE) there are no HAR-approval available (X07V2-K)! 
Conductor  fine-wired core of tinned copper strands acc. to IEC 60228 resp. VDE 0295, Class 5 
    UL 758 and CSA C22.2 
Core insulation  special PVC based compound 
Electrical properties 
Nominal voltage   HAR H07V2-K  U
0
/U:  450 / 750 V AC 
  UL (MTW)/CSA (TEW)  U:  600 V 
  UL (AWM):  U:  1000 V 
Test voltage  2500 V AC 
Mechanical and thermal properties 
Min. bending radius  fixed installation:  OD≤8 mm:    4 x OD** / 2 x OD*** 
    8<OD≤12 mm:  5 x OD** / 3 x OD*** 
    OD>12 mm:    6 x OD** / 4 x OD*** 
  ** at conventional usage; *** at cautious bending 
Temperature range  fixed installation:   HAR, (UL) MTW:   -40 °C up to +90 °C max. conductor temp. 
    UL (AWM), CSA (TEW):  -40 °C up to +105 °C max. conductor temp. 
Flame resistance  HAR:  IEC 60332-1-2 resp. VDE 0482-332-1-2  
  UL:  VW-1 
  CSA:  FT1 
Oil resistance  UL/CSA:  60°C oil rating  
Tests    acc. to IEC 60811 resp. VDE 0473 and VDE 0472, UL 1581 and CSA C22.2 
EC directive  This cable is conform to EC-Directives 2006/95/EC (Low Voltage Directive) and 
  2011 / 65 / EU (RoHS, Restriction of the use of certain hazardous substances). 