Data Sheet
U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CLASSIC FD 810 P
DB 0026300
valid from: 2014-02-21
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB0026300EN
Page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC FD 810 P cables are oil resistant high-flexible control cables with an outer sheath of Polyurethane for
flexible use and fixed installation subject to medium mechanical stress. They are among others designed for use in dry,
damp or wet rooms. Considering the indicated temperature range an outdoor use is possible. ÖLFLEX
FD CLASSIC 810 P
cables are increased oil resistant and at room temperature widely resistant to acids and caustic solutions. The outer sheath
is resistant against high mechanical stress, particularly to abrasion and scouring, cut resistant, microbe-proof and hydrolysis
resistant. They are especially for use in power chains and in permanently moved machine parts. Usage of these cables in
moving cable carriers or on motor drum guidance or under a tensile strain of more than 15 N/mm
2
conductor cross-section
is not allowed.
Application range:
in power chains or moving machine parts; particularly in wet areas of machine tools and transfer lines; mechanical engineer-
ing; suitable for use in measuring, control and regulating circuits; power circuits for electrical equipment used in automation
engineering
Design
Design based on
DIN EN 50525-2-51 resp. VDE 0285-525-2-51
DIN EN 50525-2-21 resp. VDE 0285-525-2-21
Conductor extra fine wire strands of bare copper acc. to IEC 60228 resp. VDE 0295, Class 6
Core insulation LAPP special PVC compound P8/1,
TI2, acc. to EN 50363-3 resp. VDE 0207-363-3, with increased requirements
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers
acc. to DIN EN 50334 resp. VDE 0293-334
Outer sheath Polyurethane compound TMPU acc. to EN 50363-10-2 resp. VDE 0207-363-10-2
colour: grey, similar RAL 7001
Electrical properties
Nominal voltage U
0
/U: 300/500 V AC
Test voltage C/C: 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 7,5 x outer diameter
fixed installation: 4 x outer diameter
Temperature range occasional flexing: - 5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Number of bending/unbending
cycles 5 mio. cycles
Travel distance 10 m
Oil resistance acc. to EN 50363-10-2 resp. VDE 0207-363-10-2
UV resistance acc. to EN ISO 4892-2-2006, method A (change of colour allowed)
Ozone resistance acc. to EN 50396 resp. VDE 0473-396, method B
Flammability flame retardant in acc. with IEC 60332-1-2 resp. VDE 0482-332-1-2
Tests acc. to IEC 60811, EN 50395, EN 50396
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive)
and 2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).