Datasheet
U.I. Lapp
GmbH
DATA SHEET
H1Z2Z2-K
DB 1023550
valid from: 25.04.2016
Originator: ALTE / PCM
approved: HAPF / PDC
Document: DB1023550EN
page 2 of 2
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.
PD 0019/2.1_11.09EN
Weathering/UV-resistance according to DIN EN 50618 Annex E
Ozone resistance according to EN 50396
Halogen free according to IEC 60754-1, IEC 60754-2
Smoke density according to IEC 61034-2, EN 61034-2
Flame retardant according to IEC 60332-1-2
Acid and alkaline resistance according to EN 60811-404 (Oxal-acid and Sodium hydroxide)
EU directives This cable is conform to the EU directive 2014/35/EU (Low Voltage Directive)
5. Installation
H1Z2Z2-K cables are not suitable for the installation underground.
The cable should be installed according to VDE 0100, part 520, IEC 60364-5-52, EN 50174-1 or comparable
standards. Long-term, permanent storage or constant use of the cables in or underwater is not permitted.
According to DIN EN 50618 applies:
Intended for use in PV installations e.g. acc. to HD 60364-7-712.
They are intended for permanent use outdoor and indoor, for free movable, free hanging and fixed installation.
Installation also in conduits and trunkings on, in or under plaster as well as in appliances. Suitable for the appli-
cation in/at equipment with protective insulation (protection class II).
They are inherently short-circuit and earth fault proof acc. to HD 60364-5-52.
6. Versions
Part.No.
Colour insulation
Colour outer sheath
Conductor cross section [mm²]
Outer diameter approx. [mm]
1023552
white
black
1 x 4
5,9
1023553
white
black
1 x 6
6,4
1023554
white
black
1 x 10
7,5
1023572
white
red
1 x 4
5,9
1023573
white
red
1 x 6
6,4
1023574
white
red
1 x 10
7,5
1023582
white
blue
1 x 4
5,9
1023583
white
blue
1 x 6
6,4
1023584
white
blue
1 x 10
7,5