Datasheet
PRODUCT INFORMATION
ÖLFLEX® CLASSIC 100 300/500 V
Classification ETIM 5: ETIM 5.0 Class-ID: EC001578
ETIM 5.0 Class-Description: Flexible cable
Classification ETIM 6: ETIM 6.0 Class-ID: EC001578
ETIM 6.0 Class-Description: Flexible cable
Core identification code: Up to 5 cores: colour-coded according to VDE 0293-308, refer
to Appendix T9
From 6 cores: ÖLFLEX® colour code, refer to Appendix T7
Conductor stranding: Fine wire according to VDE 0295,
class 5/IEC 60228 class 5
Torsion movement in WTG: TW-0 & TW-1, refer to Appendix T0
Minimum bending radius: Occasional flexing: 15 x outer diameter
Fixed installation: 4 x outer diameter
Nominal voltage: U0/U: 300/500 V
Test voltage: 4000 V
Protective conductor: G = with GN-YE protective conductor
X = without protective conductor
Temperature range: Occasional flexing: -5°C to +70°C
Fixed installation: -40°C to +80°C
Note
Unless specified otherwise, the shown product values are nominal values. Detailed values (e.g. tolerances) are available upon
request.
Copper price basis: EUR 150/100 kg. Refer to catalogue appendix T17 for the definition and calculation of copper-related
surcharges.
Please find our standard lengths at: www.lappkabel.de/en/cable-standardlengths
Packaging size: coil ≤ 30 kg or ≤ 250 m, otherwise drum
Please specify the preferred type of packaging (e.g. 1 x 500 m drum or 5 x 100 m coils).
Single lengths for sizes: ≥ 5G50 max. 500 m; ≥ 5G95 max. 400; ≥ 3G120 max. 500 m; ≥ 4G120 max. 300; ≥ 4G185 max. 250 m
Photographs and graphics are not to scale and do not represent detailed images of the respective products.
Prices are net prices without VAT and surcharges. Sale to business customers only.
Last Update (03.07.2020) 2 / 5
©2020 Lapp Group - Technical changes reserved