Landis+Gyr Chapter 2 - Configuration & Testing
Gridstream SCADA/DA S4SBR 98-1138 Rev AD 21
NOTE: All RF Mesh radios ship with a default Network ID, or CRC, of 670. In order to communicate
with the Gridstream S4SBR, your local radio will have to be re-configured to match the Network ID
(default 670) of the Gridstream S4SBR.
After re-configuring the Gridstream S4SBR to match the customer’s unique Network ID, the local
radio will need to be reset to its original network ID. See below or see “Assigning a New Network ID
to a Gridstream S4SBR” on page 22 for viewing the steps to re-configure the local radio.
Assign the Network ID (CRC) of the Gridstream S4SBR
All Gridstream SBRs ship with a default network ID, or CRC, of 670. In order to communicate with
other radios in a customer's network, the Gridstream S4SBR will have to be re-configured to match
the customer's unique network ID.
NOTE: Prior to operation, a Network ID / CRC must be assigned. Network ID / CRC parameters are
unique and are assigned for each customer. Please call Landis+Gyr Customer Service if you require
a Network ID / CRC.
1. From the RadioShop home screen, select Configure | Change Network Id (CRC). The
Network ID Wizard dialog will open,
2. Select Use an Existing Network and click Next to continue.
Figure 2 - 3. Network ID Wizard
The Choose an Existing Network dialog is displayed.
Figure 2 - 4. Choose an Existing Network
3. Choose a Network ID from the Available Networks drop-down list.