UtiliNet SCADA Single Board Radio 98-1546 Rev AA 33
Memory Location
[7702-7703h] Analog to Digital Channel A1.
When A1 is set to "Analog to Digital" (Bit 2) this location will contain a 10-bit reading. The scale on
this board is from 0 to 2.5 volts. Voltages greater than 2.5 VDC will be reported as 2.5 VDC.
[7704-7705h] Analog to Digital Channel A2.
When A2 is set to "Analog to Digital" (Bit 6) this location will contain a 10-bit reading. The scale on
this board is from 0 to 2.5 volts. Voltages greater than 2.5 VDC will be reported as 2.5 VDC.
[7706-7709h] D1 Interrupt Counter.
If D1 is configured as an interrupt (bit 2-3) then this location will count the number of interrupts that
have been detected.
The interrupt counter is cleared each time interrupts are enabled.