Installation Guide
3
CWE 6060 Remote Installation Guide 98-1551 15
Testing the Endpoint
After you have completed the installation process, test the installation by passing an RF Buster
magnet near the endpoint’s sensor. The CWE tests the connection to the register and transmits a
pattern to indicate if the installation is good or bad. The RF Buster detects the transmission pattern,
beeps and lights the LED.
1 ActivatetheCWEbypassingtheRFBustermagnetagainstthesideoftheCWEhousingasthe
arrowindicates.
Figure 3 - 1. CWE Activation Using RF Buster
2PressandholdthebuttonontheRFBuster.PositiontheRFBusterlessthan6inchesawayfrom
thefrontoftheCWE.TheRFBustermakesaudiblebeepsandtheLEDflashestoconfirm
transmissionofanRFpacketfromtheendpoint.
3IftheRFBusterdetects6‐10
packetswithin1minute,theinstallationisgoodandtheendpoint
hasbeenactivatedproperly.IftheRFBusterdetects3orfewerpackets,itindicatesabad
connectionbetweentheendpointandtheregister ,abadregister,abadendpoint,oranincorrect
configuration.Iftheproblempersists,refer
toTroubleshooting.
4 Attachthecoverusingthefourscrewsincludedinthehardwarekit.
5Cleantheareaandremovealldisposablematerials.
Caution: If you hold the RF Buster magnet near the side of the CWE for more than 2
seconds, it will not transmit the installation test pattern. If you do not hear beeps, hold the
RF Buster away from the CWE for 15 seconds to allow it to reset to normal operating mode.
Do not use a cell phone or any other RF device while conducting this test.
RFBuster
magnet